Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BEHLEN TECHNOLOGY & MANUFACTURING

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of BEHLEN TECHNOLOGY & MANUFACTURING in 3838 S. 108TH ST., OMAHA, NE 68144 (NAICS 333519). OSHA activity number 343683728.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Behlen Technology & Manufacturing — free Get an email when a new federal OSHA severe-injury report for Behlen Technology & Manufacturing is published. One employer, no account, unsubscribe in one click.
Site address
3838 S. 108TH ST.
City
OMAHA
State
NE
ZIP
68144
Mailing
3838 S. 108TH ST., OMAHA, NE 68144
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333519
Employees
75
Ownership type
A

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
May 15, 2019
Abate by
Jun 11, 2019
Penalty
Initial $8,335 · Current $8,126 Reduced
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    The employer is failing to protect employees from electrical hazards.  This was most recently documented on December 27, 2019 at 3838 S. 108th St. Omaha, Nebraska in that;      a) The employer had two extension cords connected together to provide power to a portable heater.       b) The employer had a 4 plex receptacle box attached to a flexible cord, the box is designed to be mounted in or on a wall.
Recent events (2)
  • — I (S) $8126
  • — Z (S) $8335

1910.305 G01 IV B

Serious Gravity 5 1 instance 2 exposed
Issued
May 15, 2019
Abate by
Jun 11, 2019
Penalty
Initial $10,419 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iv)(B):     Extension cords where run through holes in walls, ceilings, or floors;    The employer is failing to protect employees from electrical hazards.  This was most recently documented on December 27, 2019 at 3838 S. 108th St. Omaha, Nebraska. The employer is failing to ensure that electrical cords are not run through walls in the Yaskawa welding robot area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $10419

1910.305 G02 II

Serious Gravity 5 1 instance 2 exposed
Issued
May 15, 2019
Abate by
Jun 11, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii):     Flexible cords were not used only in continuous lengths without splice or tap:    The employer is failing to protect employees from electrical shock hazards. This was most recently documented on December 27, 2019 at 3838 S. 108th St. Omaha, Nebraska.  The employer failed to ensure that an extension cord that had been spliced was not utilized to power to a space heater being used by the Yaskawa robotic welder.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A04

Serious Gravity 5 1 instance 2 exposed
Issued
May 15, 2019
Abate by
Jun 11, 2019
Penalty
Initial $8,335 · Current $0 Reduced
29 CFR 1910.334(a)(4):     Portable electric equipment and flexible cords that was used in highly conductive work locations (such as those inundated with water or other conductive locations) or in job locations where employees were likely to contact water or conductive liquids were not approved for those locations:    The employer is failing to ensure that employees are not exposed to electric shock hazards.  This was most recently observed on December 27, 2019 at 3838 S. 108th St. Omaha, Nebraska. The employer is failing to ensure that electrical cords used in wet areas were approved for this location.  Electrical cords were being used with 4X4 metal enclosure and spliced in areas were water was pooling on the ground.  These cords were ran through the water.
Recent events (2)
  • — I (S) $0
  • — Z (S) $8335

1910.147 C06 I

Other-than-serious 1 instance 75 exposed
Issued
May 15, 2019
Abate by
Jul 2, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i):   The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  The employer failed to meet the requirements of this subpart.  This was most recently observed on December 27, 2018 at 3838 S 108th St.  Omaha Nebraska.  The employer was not conducting periodic inspections of it's energy control procedures for equipment with multiple energy sources.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Behlen Technology & Manufacturing's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343683728.