PORTLAND, OR ·
OSHA Inspection: VETERANS HEALTH ADMINISTRATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VETERANS HEALTH ADMINISTRATION in 3710 SW VETERANS HOSPITAL ROAD, PORTLAND, OR 97239 (NAICS 622110). OSHA activity number 343909990.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VETERANS HEALTH ADMINISTRATION
- Site address
- 3710 SW VETERANS HOSPITAL ROAD
- City
- PORTLAND
- State
- OR
- ZIP
- 97239
- Mailing
- PO BOX 1034, PORTLAND, OR 97239
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 5000
- Ownership type
- Federal government (D)
Citations
13 citations on file for this inspection.
1910.22 A03
- Issued
- Jul 9, 2019
- Abate by
- Aug 2, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(3): (3) Walking-working surfaces were not maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice: (a) on or about 3/15/2018 and at times prior thereto, employees were exposed to tripping hazards in that a hole in the walking-working surface in the generator room was not covered or guarded.
Recent events (1)
- · Z (S) $0
1910.36 D01
- Issued
- Jul 9, 2019
- Abate by
- Aug 2, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: (a) on or about 3/15/2018 and at times prior thereto, employees were exposed to hazards of smoke and flame exposure in that an exit door was marked as automatic opening and yet it was dead-bolted
Recent events (1)
- · Z (S) $0
1910.37 B02
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": (a) On or about 3/14/2019, and at times prior thereto workers were exposed to hazards of smoke and burns in at least 5 exit doors were not marked "exit" including in the elevator machinery room, the kitchen storage area, 10A-103, and 7-D dialysis room.
Recent events (1)
- · Z (S) $0
1910.37 B04
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to hazards of burns and smoke inhalation in that the direction of travel to the exit or exit discharge was not immediately apparent, in numerous areas, including the vestibule of each service-use elevator landing, the exit from the top-floor elevator machinery room, the kitchen prep area, and the exit to the parking garage.
Recent events (1)
- · Z (S) $0
1910.212 A01
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to entanglement hazards in that flywheels on the elevator motors were exposed to human contact.
Recent events (1)
- · Z (S) $0
1910.303 G02 I
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any other means: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to electric shock hazards in that live electrical contacts on the elevator motors were exposed to human contact.
Recent events (1)
- · Z (S) $0
1910.215 A04
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to struck by hazards from the grinding wheel in that the work rest was improperly adjusted approximately 3/8"
Recent events (1)
- · Z (S) $0
1910.215 B09
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: a) On or about 3/14/2019, and at times prior thereto workers were exposed to struck by hazards from the abrasive grinding wheel in that the tongue guard was adjusted to approximately 1/2"
Recent events (1)
- · Z (S) $0
1910.1030 D02 I
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(d)(2)(i): Engineering and work practice controls were not used to eliminate or minimize employees exposure: On or about 3/14/2019, and at times prior thereto workers were exposed to needlestick hazards in that they were using non-safety engineered vacutainer sharps: (a) Green plastic Vacutainer blood collection needles, found in at least 3 locations, including patient prep rooms, supply storage, and Supply Chain Management room B1C-128 (b) Blue plastic Vacutainer blood collection needles, found in supply room B1C-142
Recent events (1)
- · Z (S) $0
1904.29 B01
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.29(b)(1): A Log of all recordable work-related injuries and illnesses (OSHA Form 300 or equivalent) was not completed in the detail as required by the regulation: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to repeat occurrences of accidents in that the OSHA 300 log was not completed in full detail with the names of previously injured workers
Recent events (1)
- · Z (O) $0
1904.35 B02 IV
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.35(b)(2)(iv): The employer removed names from the OSHA 300 Log prior to making copies of the Log available to any representative or employee who requested access. (a) On or about 3/14/2019, and at times prior thereto workers were exposed to repeat occurrences of accidents in that the OSHA 300 log was not completed in full detail with the names of previously injured workers.
Recent events (1)
- · Z (O) $0
1910.303 B02
- Issued
- Jul 9, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to hazards of burns and smoke inhalation in that relocatable power taps was plugged into another relocatable power tap.
Recent events (1)
- · Z (O) $0
1910.1030 G01 I C
- Issued
- Jul 9, 2019
- Abate by
- Aug 2, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(g)(1)(i)(C): Labels required by 29 CFR 1910.1030 were not fluorescent orange or orange-red, or predominantly so, or with lettering or symbols in a contrasting color: (a) On or about 3/14/2019, and at times prior thereto workers were exposed to infectious hazards in that in the Research Lab biohazard warning labels affixed to the minus 80 degree F freezers were black and white.
Recent events (1)
- · Z (O) $0
More inspections at Veterans Health Administration
View Veterans Health Administration's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343909990.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.