SYRACUSE, NY —
OSHA Inspection: SYRACUSE UNIVERSITY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SYRACUSE UNIVERSITY in 111 COLLEGE DRIVE 5TH FLOOR PENTHOUSE, SYRACUSE, NY 13209 (NAICS 611310). OSHA activity number 343982922.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SYRACUSE UNIVERSITY
- Site address
- 111 COLLEGE DRIVE 5TH FLOOR PENTHOUSE
- City
- SYRACUSE
- State
- NY
- ZIP
- 13209
- Mailing
- 285 AINSLEY DR, SYRACUSE, NY 13209
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 611310
- Employees
- 3650
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.147 C04 I
- Issued
- Oct 17, 2019
- Penalty
- Initial $13,260 · Current $7,956 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section a) Science & Technology Center, Penthouse Utility Room, on or about 4/17/2019: Procedures were not utilized for the control of potentially hazardous energy while an employee was servicing the cooling tower fans.
Recent events (2)
- — I (S) $7956
- — Z (S) $13260
1910.147 C08
- Issued
- Oct 17, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(8): Lockout or tagout was not performed only by the authorized employees who are performing the servicing or maintenance: a) Science & Technology Building, Penthouse Utility Room, on or about 4/17/19: An authorized employee was performing maintenance activities on the cooling tower fans and did not personally and physically lockout the equipment at the source. The authorized employee relied on another employee working in the Emergency Management Systems Control Room to turn the fans off by computer. The unexpected start up of the fan resulted in a finger tip amputation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C07 I
- Issued
- Oct 17, 2019
- Penalty
- Initial $13,260 · Current $7,956 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees: a) Syracuse University, Facilities Services, on or about 4/17/19: The employer did not ensure that affected and authorized employees understood the purpose and function of the energy control program and that they acquired the knowledge and skills required for the safe application, usage and removal of the energy controls.
Recent events (2)
- — I (S) $7956
- — Z (S) $13260
More inspections at Syracuse University
View Syracuse University's full OSHA safety record →
More inspections in this industry (NAICS 611310)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343982922.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.