Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: IBAKEFOODS, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of IBAKEFOODS, LLC in 256 BAKER STREET, RIMERSBURG, PA 16248 (NAICS 311821). OSHA activity number 344076500.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ibakefoods, LLC — free Get an email when a new federal OSHA severe-injury report for Ibakefoods, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
IBAKEFOODS, LLC
Site address
256 BAKER STREET
City
RIMERSBURG
State
PA
ZIP
16248
Mailing
256 BAKER STREET, RIMERSBURG, PA 16248
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311821
Employees
60
Ownership type
A

11 citations on file for this inspection.

1910.157 G01

Serious Gravity 1 1 instance 60 exposed
Issued
Jul 5, 2019
Abate by
Aug 9, 2019
Penalty
Initial $3,580 · Current $2,506 Reduced
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:   A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, on or about June 12, 2019 and times prior thereto:  Employees were provided with, and permitted to use, portable dry chemical fire extinguishers.  Employees did not have fire extinguisher training.
Recent events (2)
  • — I (S) $2506
  • — Z (S) $3580

1910.157 C01

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, maintenance shop area, on or about June 12, 2019 and times prior thereto:  Items, including, but not limited to, a pedestal fan were stored in front of an Amerex B456 dry chemical fire extinguisher (S/N:  BM-443280).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 E02

Serious Gravity 1 1 instance 60 exposed
Issued
Jul 5, 2019
Abate by
Aug 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, on or about June 12, 2019 and times prior thereto:  Employees were provided with, and permitted to use, portable dry chemical fire extinguishers.  The employer did not visually inspected the portable fire extinguishers at least monthly.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $3,580 · Current $2,506 Reduced
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, maintenance shop, on or about June 12, 2019 and times prior thereto:  A flexible cord was spliced into an electrical breaker box in the maintenance shop and was ran to a stretch wrapping machine in the wareroom.  B.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, sanitation room, on or about June 12, 2019 and times prior thereto:  The electrical cover plate for an electrical outlet box was not securely affixed to the box.
Recent events (2)
  • — I (S) $2506
  • — Z (S) $3580

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, packing room at the six pack wrapper, on or about June 12, 2019 and times prior thereto:  Employees were plugging equipment including, but not limited to, a VIAjet L12 thermal inkjet printer (S/N:  02628) and a CTM labeling system (S/N:  360a-2750-1801) into a metallic electrical knockout pendant box.  The metallic electrical knockout box was not being used as it was listed and labelled.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV

Serious Gravity 1 2 instances 1 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv):  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, from the maintenance shop to the wareroom, on or about June 12, 2019 and times prior thereto:  A flexible cord was spliced into an electrical breaker box in the maintenance shop and was ran to a stretch wrapping machine in the wareroom.  The flexible cord was used as a substitute for the fixed wiring of the structure, attached to building surfaces, and was ran through a doorway.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 G02

Other-than-serious 1 instance 1 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, sanitation room, on or about June 12, 2019 and times prior thereto:  Employees enter an electrical breaker panel cage area to turn on breakers for equipment including, but not limited to, metal dough tub and a pallet of boxes.  The path of egress from the electrical breaker panel cage area was 12-inches.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C07 I B

Other-than-serious 1 instance 60 exposed
Issued
Jul 5, 2019
Abate by
Aug 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i)(B): Affected employees were not instructed in the purpose and use of the energy control procedure:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, on or about June 12, 2019 and times prior thereto:  Employees perform service and maintenance activities at the facility.  Employees are not provided with affected employee training.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 Q07

Other-than-serious 1 instance 3 exposed
Issued
Jul 5, 2019
Abate by
Aug 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.178(q)(7): Industrial trucks were not examined before being placed in service:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, on or about June 12, 2019 and times prior thereto:  Employees operate powered industrial trucks on-site.  Employees are not performing an examination of the truck daily prior to use.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 1 instance 2 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, packing room, on or about June 12, 2019 and times prior thereto:  Breakers within an electrical breaker panel, including, but not limited to, breaker #1, #3, #4, #6, #8, #9, #11-#14, and #17-#22, were not identified as to their purpose.  B.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, maintenance shop area, on or about June 12, 2019 and times prior thereto:  Breakers within an electrical breaker panel, including, but not limited to, breaker #1-#3, #9, #10, #12, #14, #16, #18, #20-#26, #34, and #36 were not identified as to their purpose.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 2 instances 2 exposed
Issued
Jul 5, 2019
Abate by
Jul 31, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  A.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, packing room, on or about June 12, 2019 and times prior thereto:  Items and equipment including, but not limited to, a Yale powered industrial truck was parked in front of two electrical breaker panel boxes.  B.)  IbakeFoods, LLC, 256 Baker Street, Rimersburg, PA  16248, maintenance shop area, on or about June 12, 2019 and times prior thereto:  Items and equipment including, but not limited to, a jack was stored in front of an electrical breaker panel box.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Ibakefoods, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344076500.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.