COLORADO SPRINGS, CO —
OSHA Inspection: SINTON DAIRY FOODS COMPANY, LLC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of SINTON DAIRY FOODS COMPANY, LLC in 3801 SINTON ROAD, COLORADO SPRINGS, CO 80907 (NAICS 424430). OSHA activity number 344217047.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SINTON DAIRY FOODS COMPANY, LLC
- Site address
- 3801 SINTON ROAD
- City
- COLORADO SPRINGS
- State
- CO
- ZIP
- 80907
- Mailing
- 3801 SINTON ROAD, COLORADO SPRINGS, CO 80907
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424430
- Employees
- 80
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 D03 I B
- Issued
- Oct 7, 2019
- Abate by
- Nov 1, 2019
- Penalty
- Initial $8,051 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process: 1) On August 5, 2019, and at prior times, the employer's P&ID was inaccurate in the following instances: a) The P&ID listed a vessel as AV315 but the vessel was labeled AV313 in the field; b) The P&ID listed a vessel as CT12 but the vessel was labeled CT 13 in the field; c) The P&ID listed a vessel as CT13 but the vessel was labeled CT 12 in the field; d) The P&ID listed an oil pot as KO 302B but the vessel did not have an ID tag in the field; e) The P&ID listed a vessel as PD302 but the vessel did not have an ID tag in the field; f) The P&ID listed two pressure relief valves, PD302-4 and PD302-8, but the valves did not have ID tags in the field; g) The P&ID listed a pressure relief valve as CT13-9 but the valve did not have an ID tag in the field; h) The P&ID listed two pressure relief valves, AV315-18 and AV315-19, but the valves did not have ID tags in the field.
Recent events (2)
- — I (O) $0
- — Z (S) $8051
1910.119 D03 I D
- Issued
- Oct 7, 2019
- Abate by
- Nov 1, 2019
- Penalty
- Initial $8,051 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Information pertaining to the equipment in the process did not include relief system design and design basis: 1) On August 5, 2019, and at prior times, the employer did not maintain an accurate relief system design and design basis in that pressure relief valves AV315-18 and AV315-19 were not included or evaluated in the employer's relief system design and design basis.
Recent events (2)
- — I (O) $0
- — Z (S) $8051
1910.119 D03 II
- Issued
- Oct 7, 2019
- Abate by
- Oct 31, 2020
- Penalty
- Initial $8,051 · Current $16,900
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices: 1) On August 5, 2019, and at prior times, the employer did not document that equipment in the process complied with recognized and generally accepted good engineering practices. The employer did not document that ventilation in the machinery room met minimum flow rates for emergency purging ventilation, such as specified by ASHRAE standard 15-2007, section 8.11.5, which the employer had designated as recognized and generally accepted good engineering practices (RAGAGEP).
Recent events (2)
- — I (S) $16900
- — Z (S) $8051
1910.307 C02 I
- Issued
- Oct 7, 2019
- Abate by
- Oct 31, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the class of location and/or for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was present: 1) On August 5, 2019, and at prior times, electrical equipment in the machinery room was not approved for use in Class 1, Division 2 locations.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Sinton Dairy Foods Company, LLC
View Sinton Dairy Foods Company, LLC's full OSHA safety record →
More inspections in this industry (NAICS 424430)
More inspections in CO
Source