Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SUNRISE FARMS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SUNRISE FARMS, INC. in 105 CAUTERSKILL RD, CATSKILL, NY 12414 (NAICS 112310). OSHA activity number 344228796.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sunrise Farms, INC. — free Get an email when a new federal OSHA severe-injury report for Sunrise Farms, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SUNRISE FARMS, INC.
Site address
105 CAUTERSKILL RD
City
CATSKILL
State
NY
ZIP
12414
Mailing
105 CAUTERSKILL RD, CATSKILL, NY 12414
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
112310
Employees
8000
Ownership type
A

5 citations on file for this inspection.

1910.37 A03

Other-than-serious 1 instance 4 exposed
Issued
Nov 19, 2019
Abate by
Nov 25, 2019
Penalty
Initial $5,683 · Current $0 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    a) Cooler Processing Room - On or about August 13, 2019, an exit route was not kept free and unobstructed with carts of product being temporarily stored in front of the exit route leaving only a space of approximately 12 inches of access.
Recent events (2)
  • — I (O) $0
  • — Z (S) $5683

1910.37 B06

Other-than-serious 1 instance 4 exposed
Issued
Nov 19, 2019
Abate by
Nov 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:    a) Cooler Processing Room - On or about August 13, 2019, an exit sign was not illuminated.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 G01 II

Other-than-serious 1 instance 2 exposed
Issued
Nov 19, 2019
Abate by
Dec 2, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a) Egg Wash Room - On or prior to August 13, 2019, a fan was stored in front of an electrical panel.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 2 instances 4 exposed
Issued
Nov 19, 2019
Abate by
Dec 16, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Cooler Processing Room - On or prior to August 13, 2019, an extension cord run through the ceiling plugged into a relocatable power tap (RPT) that powered a Craig Speaker Tower plugged into the RPT was being used as a substitute for fixed wiring.  b) Cooler Processing Room - On or prior to August 13, 2019, an extension cord run through the ceiling plugged into a relocatable power tap (RPT) that powered a Marsh TD2100 taper machine plugged into the RPT was being used as a substitute for fixed wiring.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV B

Other-than-serious 2 instances 4 exposed
Issued
Nov 19, 2019
Abate by
Dec 16, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:  a) Cooler Processing Room - On or prior to August 13, 2019, an extension cord was run through the ceiling plugged into a relocatable power tap (RPT) that powered a Craig Speaker Tower plugged into the RPT.  b) Cooler Processing Room - On or prior to August 13, 2019, an extension cord was run through the ceiling plugged into a relocatable power tap (RPT) that powered a Marsh TD2100 taper machine plugged into the RPT.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Sunrise Farms, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344228796.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.