BROOKLYN, NY —
OSHA Inspection: LEECO CONSTRUCTION CORP.
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of LEECO CONSTRUCTION CORP. in 297 GRAND ST., BROOKLYN, NY 11211 (NAICS 236116). OSHA activity number 344238902.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LEECO CONSTRUCTION CORP.
- Site address
- 297 GRAND ST.
- City
- BROOKLYN
- State
- NY
- ZIP
- 11211
- Mailing
- 214 25TH ST, BROOKLYN, NY 11232
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236116
- Employees
- 2
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.403 I02 I
- Issued
- Feb 12, 2020
- Abate by
- Feb 21, 2020
- Penalty
- Initial $3,181 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. a) 3rd floor: Employees used an outlet box to energize electric powered hand tools to install flooring and drywalls. The outlet box was missing a cover. Live parts were exposed and not guarded against accidental contact by any form of enclosure. On or about 08/16/19.
Recent events (2)
- — I (S) $1960
- — Z (S) $3181
1926.404 B01 I
- Issued
- Feb 12, 2020
- Abate by
- Feb 21, 2020
- Penalty
- Initial $3,181 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. a) 3rd floor: Employees used electric powered hand tools to install flooring and drywalls. The tools were connected to extension cords, which were routed to a nearby outlet device and were not provided with a ground fault circuit interrupter. On or about 08/16/19.
Recent events (2)
- — I (S) $1960
- — Z (S) $3181
1926.404 F06
- Issued
- Feb 12, 2020
- Abate by
- Feb 21, 2020
- Penalty
- Initial $3,181 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous. a) 3rd floor: Employees used electric powered hand tools to install flooring and drywalls. The tools were connected to extension cords, which were routed to a nearby outlet device and were missing ground pins. On or about 08/16/19.
Recent events (2)
- — I (S) $1960
- — Z (S) $3181
1926.405 G02 IV
- Issued
- Feb 12, 2020
- Abate by
- Feb 21, 2020
- Penalty
- Initial $3,181 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: a) 3rd floor: Employees used electric powered hand tools to install flooring and drywalls. The tools were connected to an extension cord, which was routed to a nearby outlet device and was not provided strain relief to its outlet end. On or about 08/16/19. b) 3rd floor: Employees used an outlet box to energize electric powered hand tools to install flooring and drywalls. The power cord for the outlet box was not provided strain relief. On or about 08/16/19.
Recent events (2)
- — I (S) $1960
- — Z (S) $3181
1926.416 E01
- Issued
- Feb 12, 2020
- Abate by
- Feb 21, 2020
- Penalty
- Initial $3,181 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used. a) 3rd floor: Employees used electric powered hand tools to install flooring and drywalls. The tools were connected to an extension cord, which was routed to a nearby outlet device and was worn and frayed with damaged insulation. On or about 08/16/19.
Recent events (2)
- — I (S) $1960
- — Z (S) $3181
More inspections at Leeco Construction Corp.
View Leeco Construction Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 236116)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344238902.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.