Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: XPO LOGISTICS SUPPLY CHAIN, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of XPO LOGISTICS SUPPLY CHAIN, INC. in 747 DOUGLAS HILL ROAD, LITHIA SPRINGS, GA 30122 (NAICS 493190). OSHA activity number 344257795.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch XPO Logistics Supply Chain, INC. — free Get an email when a new federal OSHA severe-injury report for XPO Logistics Supply Chain, INC. is published. One employer, no account, unsubscribe in one click.
Site address
747 DOUGLAS HILL ROAD
City
LITHIA SPRINGS
State
GA
ZIP
30122
Mailing
747 DOUGLAS HILLS ROAD, LITHIA SPRINGS, GA 30122
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493190
Employees
400
Ownership type
A

2 citations on file for this inspection.

1910.303 B02

Other-than-serious 2 instances 10 exposed
Issued
Feb 14, 2020
Abate by
Mar 5, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a.  Production Area, Line 2:  On or about August 23, 2019, and at times prior, the employer exposed employees to electric shock hazards, in that a 4 inch by 4 inch metal electrical box was used as a pendant receptacle and was used to provide power to a Triangle Engineering of Arkansas, Inc. 36 inch fan.  b.  Production Area, Office Shed by Line 2:  On or about August 23, 2019, and at times prior, the employer exposed employees to electric shock hazards, in that a Underwriter's Laboratory listed and labeled relocatable power tap (RPT) supplying power to a TPI Corporation pedestal fan was not used in accordance with the guidelines of the listing and labeling agency where the RPT was attached to the building surfaces with cable ties.
Recent events (1)
  • — Z (O) $0

1910.304 G05

Other-than-serious 2 instances 10 exposed
Issued
Feb 14, 2020
Abate by
Mar 5, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a.  Production Area, Line 1:  On or about August 23, and at times prior, the employer exposed employees to electric shock hazards, in that a TPI Corporation pedestal fan provided for personal cooling on the production lines was operated with the ground pin removed from the plug.  b.  Production Area, Line 2:  On or about August 23, and at times prior, the employer exposed employees to electric shock hazards, in that a Triangle Engineering of Arkansas, Inc. 36 inch fan provided for personal cooling on the production lines was operated with the ground pin removed from the plug.
Recent events (1)
  • — Z (O) $0

View XPO Logistics Supply Chain, INC.'s full OSHA safety record →