Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SCHULT INDUSTRIES

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of SCHULT INDUSTRIES in 900 NW HUNTER DR, BLUE SPRINGS, MO 64015 (NAICS 339950). OSHA activity number 344287339.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Schult Industries — free Get an email when a new federal OSHA severe-injury report for Schult Industries is published. One employer, no account, unsubscribe in one click.
Establishment
SCHULT INDUSTRIES
Site address
900 NW HUNTER DR
City
BLUE SPRINGS
State
MO
ZIP
64015
Mailing
900 NW HUNTER DRIVE, BLUE SPRINGS, MO 64015
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339950
Employees
150
Ownership type
A

4 citations on file for this inspection.

1910.305 A02

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 10, 2020
Abate by
Feb 6, 2020
Penalty
Initial $5,115 · Current $3,581 Reduced

Hazardous substances 8870

29 CFR 1910.305(a)(2): Temporary electrical power and lighting installations of 600 volts, nominal, or less were used for purposes other than those permitted in subparagraphs (a), (b) and (c) of this paragraph:  At a worksite located at 900 NW Hunter Dr., Blue Springs, MO: Employees were exposed to electrical shock hazards. A two receptacle extension cord was in operations and had bee permanently affixed to a wall in the shop. The extension cord was being used to power a Maxx Air portable fan for a duration in excess of what is approved by this regulation.
Recent events (2)
  • — I (S) $3580.5
  • — Z (S) $5115

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 10, 2020
Abate by
Feb 6, 2020
Penalty
Initial $8,525 · Current $5,968 Reduced

Hazardous substances 8870

29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  At a worksite located at 900 NW Hunter Dr., Blue Springs, MO: Employees were exposed to electric shock hazards. Employees were working in an area of the shop where portable fans were in use. One of the Maxx Air portable fans was in use and was pulled away from the strain relief device thereby increasing the risk of the conductor wires separating from the terminal.
Recent events (2)
  • — I (S) $5967.5
  • — Z (S) $8525

1910.334 A02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 10, 2020
Abate by
Feb 6, 2020
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  At a worksite located at 900 NW Hunter Dr., Blue Springs, MO: Employees were exposed to electric shock hazards. Employees were working in an area of the shop where portable fans were in use. One of the Maxx Air portable fans was in use and had not been inspected for any external defects. The cord showed a section that was damaged and had been covered by electrical tape.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 10, 2020
Abate by
Feb 6, 2020
Penalty
Initial $8,525 · Current $5,968 Reduced

Hazardous substances 8870

29 CFR 1910.334(a)(2)(iii): 29 CFR 1910.334(a)(2)(iii): Where a connection plug is to be connected to a receptacle, the ratio of the plug and receptacle contacts was not checked first to ensure that the plug and receptacle contacts were of the appropriate coupling settings:  At a worksite located at 900 NW Hunter Dr., Blue Springs, MO: Employees were exposed to electric shock hazards. Employees were working in an area of the shop where portable fans were in use. One of the Maxx Air portable fans was in use and plugged into an extension cord that only had two receptacle contacts. The cord equipment had three receptacle contacts and the ground pin was bypassed to allow for the connection to take place.
Recent events (2)
  • — I (S) $5967.5
  • — Z (S) $8525

View Schult Industries's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344287339.