OSHA Inspection: INGRAM CONCRETE, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of INGRAM CONCRETE, LLC in 1601 SW SHERIDAN ROAD, LAWTON, OK 73505 (NAICS 327320). OSHA activity number 344364880.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ingram Concrete, LLC — free Get an email when a new federal OSHA severe-injury report for Ingram Concrete, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1601 SW SHERIDAN ROAD
City
LAWTON
State
OK
ZIP
73505
Mailing
1601 SW SHERIDAN ROAD, LAWTON, OK 73505
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327320
Employees
6
Ownership type
A

3 citations on file for this inspection.

1910.305 G01 IV A

Serious Gravity 5 2 instances 4 exposed
Issued
Dec 10, 2019
Abate by
Jan 7, 2020
Penalty
Initial $2,273 · Current $1,364 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   On or about October 07, 2019, and at times prior thereto, flexible cords were used as a substitute for fixed wiring in the following instances:   a) Chemical storage room - a flexible cord was used in lieu of permanent wiring to power a security camera in the work area. Employees were exposed to the hazard of electrical shock.   b) Office hallway - a flexible cord was used in lieu of permanent wiring to power a HVAC furnace in the office building. Employees were exposed to the hazard of electrical shock.
Recent events (2)
  • — I (S) $1363.8
  • — Z (S) $2273

1910.303 F02

Other-than-serious 2 instances 4 exposed
Issued
Dec 10, 2019
Abate by
Jan 7, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  On or about October 07, 2019, and at times prior thereto, disconnecting means or overcurrent devices were not labeled to identify its purpose in the following instances:   a) Chemical Storage Room - disconnecting means or overcurrent devices were not labeled to identify its purpose. Employees were exposed to the hazard of electrical shock.    b) Mechanic Shop - disconnecting means or overcurrent devices were not labeled to identify its purpose. Employees were exposed to the hazard of electrical shock.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 II

Other-than-serious 1 instance 4 exposed
Issued
Dec 10, 2019
Abate by
Jan 7, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   Mechanic Shop. On or about October 07, 2019, and at times prior thereto, an electrical panel boxes was found that had open knockouts that had not been effectively closed. Employees were exposed to the hazard of electrical shock.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Ingram Concrete, LLC's full OSHA safety record →