Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EVERSOURCE ENERGY SERVICE COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EVERSOURCE ENERGY SERVICE COMPANY in STATION 980 TUPPER RD., SANDWICH, MA 02563 (NAICS 221122). OSHA activity number 344368675.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Eversource Energy Service Company — free Get an email when a new federal OSHA severe-injury report for Eversource Energy Service Company is published. One employer, no account, unsubscribe in one click.
Site address
STATION 980 TUPPER RD.
City
SANDWICH
State
MA
ZIP
02563
Mailing
107 SELDEN ST., BERLIN, CT 06037
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
8084
Ownership type
A

5 citations on file for this inspection.

1926.950 B01 I

Deleted Serious Gravity 10 5 instances 5 exposed
Issued
Mar 18, 2020
Abate by
Mar 26, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1926.950(b)(1)(i): Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this subpart that pertain to his or her job assignments.  Location: the yard @ Station 980, Tupper Rd. East Sandwich, MA  On or about October 8, 2019 employees were exposed to electrical hazards, where the employees were not trained in, and familiar with, the present grounding cable assembly requirements for substation buss voltages in the canal switch station.
Recent events (3)
  • — F (S) $0
  • — C (S) $13494
  • — Z (S) $13494

1926.950 D03

Deleted Serious Gravity 10 5 instances 5 exposed
Issued
Mar 18, 2020
Abate by
Mar 26, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1926.950(d)(3): 29 CFR 1926.950 (d)(3):  The presence of hazardous induced voltages had not been determined before work on or near the lines or equipment is started:  Location: The yard @ Station 980, Tupper Rd. East Sandwich, MA  On or about October 8, 2019 employees were exposed to electrical hazards, where induced voltages had not been determined before work on or near the lines or equipment was started.
Recent events (3)
  • — F (S) $0
  • — C (S) $13494
  • — Z (S) $13494

5(a)(1)

Serious Gravity 10 5 instances 5 exposed
Issued
Mar 18, 2020
Abate by
Oct 20, 2021
Penalty
Initial $0 · Current $13,494
OSH ACT of 1970 Section (5)(a)(1)  The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees:  Location: The yard @ Station 980, Tupper Rd. East Sandwich, MA  On or about October 8, 2019, a grounding cable was clamped to a mechanically incorrect grounding clamp, posing a risk that if the cable were to fall out of the grounding clamp without the  hot end first being removed with a live line tool and without the employee wearing gloves protective against the current created by the voltage induced in the line, the employee would be exposed to a recognized  hazard causing or likely to cause death or serious physical harm, contrary to section 5(a)(1) of the Act.
Recent events (3)
  • — F (S) $13494
  • — C (S) $0
  • — Z (S) $0

1926.960 C01 III A

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Mar 18, 2020
Abate by
Mar 26, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1926.960(c)(1)(iii)(A): Employees were not insulated from energized parts through the use of rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (c)(2) of this section:  Location: The yard @ Station 980, Tupper Rd. East Sandwich, MA  On or about October 8, 2019 an employee received an electrical shock, where the employer or a team leader did not ensure the employee was insulated from energized parts through the use of rubber insulating gloves and sleeves.
Recent events (3)
  • — F (S) $0
  • — C (S) $13494
  • — Z (S) $13494

1926.966 F03

Deleted Serious Gravity 10 5 instances 5 exposed
Issued
Mar 18, 2020
Abate by
Mar 26, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1926.966(f)(3): Temporary removal of guards. Before guards are removed from energized equipment, the employer shall install barriers around the work area to prevent employees who are not working on the equipment, but who are in the area, from contacting the exposed live parts.  Location: The yard @ Station 980, Tupper Rd. East Sandwich, MA  On or about October 8, 2019 employees were exposed to electrical hazards, where the employer did not ensure barriers were properly installed around the work area to prevent employees who were not working on the equipment from entering the area.
Recent events (3)
  • — F (S) $0
  • — C (S) $13494
  • — Z (S) $13494

View Eversource Energy Service Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344368675.