Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TAMPA ELECTRIC COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TAMPA ELECTRIC COMPANY in 9995 STATE ROAD 37 SOUTH, MULBERRY, FL 33860 (NAICS 221122). OSHA activity number 344370259.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tampa Electric Company — free Get an email when a new federal OSHA severe-injury report for Tampa Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
9995 STATE ROAD 37 SOUTH
City
MULBERRY
State
FL
ZIP
33860
Mailing
702 N. FRANKLIN ST. PLAZA 4, TAMPA, FL 33602
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
221122
Employees
75
Ownership type
A

4 citations on file for this inspection.

1910.269 D06 VII

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 24, 2020
Penalty
Initial $10,603 · Current $10,603
29 CFR 1910.269(d)(6)(vii): Prior to starting work on machines or equipment that had been locked out or tagged out, the authorized employee did not verify that isolation and deenergization of the machine or equipment had been accomplished:  a. On or about October 07, 2019, at the Polk station Unit 2, CT-4, boiler feed water suction strainer, employees were exposed to steam and super-heated water, in that, while conducting maintenance on the boiler feed water suction strainer did not verify that isolation of pressure and thermal energy were brought to a safe state by allowing steam and water to cool off at safe levels.
Recent events (2)
  • — C (S) $10603
  • — Z (S) $10603

1910.269 D02 IV D

Repeat Gravity 5 1 instance 2 exposed
Issued
Mar 24, 2020
Penalty
Initial $53,015 · Current $53,015
29 CFR 1910.269(d)(2)(iv)(D): The procedure did not clearly and specifically outline specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures:   a. On or about October 07, 2019, at the Polk station Unit 2, CT-4, boiler feed water suction strainer, employees were exposed to steam and super-heated water under pressure, in that, while conducting maintenance on the boiler feed water suction strainer the lockout procedure used did not include steps in testing and establishing that all sources of energy such as pressure and thermal energy were brought to a safe state.   Tampa Electric Company was previously cited for a violation of this Occupational Safety and Health Standard 1910.269(d)(2)(iv)(D) which was contained in OSHA inspection number 1273624, citation number 1, item number 3b and was affirmed as a final order on 04/22/2019, with respect to a workplace located at 13031 Wyandotte Rd, Apollo Beach, FL, 33572.
Recent events (2)
  • — C (R) $53015
  • — Z (R) $53015

1910.269 D06 I

Repeat Gravity 5 1 instance 2 exposed
Issued
Mar 24, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(6)(i): Before an authorized or affected employee turned off a machine or equipment, the authorized employee did not have knowledge of the type and magnitude of the energy, the hazards of the energy to be controlled, and the method or means to control the energy.   a. On or about October 07, 2019, at the Polk station Unit 2, CT-4, boiler feed water suction strainer, employees were exposed to steam and super-heated water, in that, while conducting maintenance on the boiler feed water suction strainer, the lockout procedure did not include the type and magnitude of all energy sources. The lockout procedure used by the employees addressed isolating and draining the system, however, the magnitude of pressure and thermal energy in the form of steam and superheated water were not addressed in the procedure.  Tampa Electric Company was previously cited for a violation of this Occupational Safety and Health Standard 1910.269(d)(6)(i), which was contained in OSHA inspection number 1273624, citation number 1, item number 3c and was affirmed as a final order on 04/22/2019, with respect to a workplace located at 13031 Wyandotte Rd, Apollo Beach, FL, 33572.
Recent events (2)
  • — C (R) $0
  • — Z (R) $0

1910.269 D02 V E

Other-than-serious 1 instance 2 exposed
Issued
Mar 24, 2020
Abate by
May 8, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(2)(v)(E): The employer did not certify that annual periodic inspections of the energy control procedures had been performed by listing the machine or equipment on which the energy control procedures were being used, the date of the inspection, the employees included in the inspection, and the person performing the inspection:   a. On or about October 07, 2019, at the Polk station Unit 2, CT-4, boiler feed water suction strainer, employees were exposed to the release of stored energy, such as steam and superheated water, in that, a certification record of the periodic annual energy control procedures was not maintained.
Recent events (2)
  • — C (O) $0
  • — Z (O) $0

View Tampa Electric Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344370259.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.