Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WORTHEN INDUSTRIES, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WORTHEN INDUSTRIES, INC. in 3 EAST SPIT BROOK ROAD, NASHUA, NH 03060 (NAICS 325520). OSHA activity number 344500962.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Worthen Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Worthen Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3 EAST SPIT BROOK ROAD
City
NASHUA
State
NH
ZIP
03060
Mailing
3 EAST SPIT BROOK ROAD, NASHUA, NH 03060
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325520
Employees
92
Ownership type
A

5 citations on file for this inspection.

1910.37 A02

Deleted Serious Gravity 5 2 instances 20 exposed
Issued
Jun 5, 2020
Abate by
Jul 10, 2020
Penalty
Initial $9,639 · Current $0 Reduced
29 CFR 1910.37(a)(2): Exit routes were not arranged so that employees would not have to travel toward a high hazard area, nor was the path of travel effectively shielded from the high hazard area by suitable partitions or other physical barriers:  a. Northeast Corner of Churn Room (Floor Level) - On or about December 10, 2019, the P2 overflow tank was located in front of the exit discharge which potentially exposed employees to fire and chemical hazards in the event of a release.  b. Northeast Corner of Churn Room (Mezzanine Level) - On or about December 10, 2019, the P2 overflow tank was located below the exit discharge which potentially exposed employees to fire and chemical hazards in the event of a release.
Recent events (3)
  • — F (S) $0
  • — C (S) $9639
  • — Z (S) $9639

1910.106 H03 I A

Deleted Serious Gravity 5 1 instance 20 exposed
Issued
Jun 5, 2020
Abate by
Jul 10, 2020
Penalty
Initial $9,639 · Current $0 Reduced
29 CFR 1910.106(h)(3)(i)(a):  Processing buildings were not of fire-resistance or noncombustible construction.  a. Churn Room - On or about December 10, 2019, overhead doors located on the outer walls were constructed of wood and did not provide fire-resistance between processing equipment and overflow tanks located directly on the other side of the doors.
Recent events (3)
  • — F (S) $0
  • — C (S) $9639
  • — Z (S) $9639

1910.119 D03 I B

Deleted Serious Gravity 5 1 instance 20 exposed
Issued
Jun 5, 2020
Abate by
Jul 10, 2020
Penalty
Initial $9,639 · Current $0 Reduced
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams (P&IDs) were not accurate and did not represent equipment that was existing and was part of the process.  a. Churn Room - On or about December 10, 2019, the vessel piping P&IDs were not accurate in that vital components were: - Missing: i) C10 Lower Piping Plan - Temperature gauge (steam out side); ii) C10 Lower Piping Plan - Temperature gauge (city supply side); iii) C10 Lower Piping Plan  - Valve between the steam trap and temperature gauge (steam out side); iv) Solvent Manifold #1 Wall Elevation South Wall-Mezzanine Level - Fusible link safety valve between solvent meter and valve; - Misplaced: v) C7 Lower Piping Plan - Dampener; vi) C7 Lower Piping Plan - Fusible link safety valve; and vii) C10 Lower Piping Plan - Fusible link safety valve.
Recent events (3)
  • — F (S) $0
  • — C (S) $9639
  • — Z (S) $9639

1910.119 D03 I E

Serious Gravity 5 1 instance 20 exposed
Issued
Jun 5, 2020
Abate by
Jul 10, 2020
Penalty
Initial $9,639 · Current $9,639
29 CFR 1910.119(d)(3)(i)(E): Information pertaining to the equipment in the process did not include a ventilation system design.  a. Site - On or about December 10, 2019, a ventilation system design basis for the churn room was not available.
Recent events (3)
  • — F (S) $9639
  • — C (S) $9639
  • — Z (S) $9639

1910.119 J05

Serious Gravity 5 2 instances 20 exposed
Issued
Jun 5, 2020
Abate by
Jul 10, 2020
Penalty
Initial $9,639 · Current $4,861 Reduced
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use:  a) Churn Room (Floor Level) - On or about December 10, 2019, product had dripped from the sample port on vessel P40 to the floor.   b) Churn Room (Mezzanine Level) - On or about January 7, 2020, a process line between the vessel ROSS and vessel P20 was open and the valve was not car-sealed.
Recent events (3)
  • — F (S) $4861
  • — C (S) $9639
  • — Z (S) $9639

View Worthen Industries, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344500962.