OSHA Inspection: ARMY CORPS OF ENGINEERS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ARMY CORPS OF ENGINEERS in THE DALLES DAM, THE DALLES, OR 97058 (NAICS 221111). OSHA activity number 344536750.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Army Corps of Engineers for free Get an email when a new federal OSHA severe-injury report for Army Corps of Engineers is published. One employer, no account, unsubscribe in one click.
Site address
THE DALLES DAM
City
THE DALLES
State
OR
ZIP
97058
Mailing
P.O. BOX 564, THE DALLES, OR 97058
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221111
Employees
130
Ownership type
Federal government (D)

8 citations on file for this inspection.

1910.37 B02

Serious Gravity 5 3 instances 100 exposed
Issued
May 13, 2020
Abate by
Jun 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit".  (a) Powerhouse - 8th floor (phase gallery) - On or about January 6, 2020 and at times prior thereto, the exit routes throughout the 8th floor including, but not limited to: bay 9 through 16 were not clearly visible, this exposed employees to fire and smoke inhalation hazards.  (b) Powerhouse - 7th floor (cable gallery) - On or about January 6, 2020 and at times prior thereto, the exit routes throughout the 7th floor including, but not limited to: bay 9 through 16 were not clearly visible, this exposed employees to fire and smoke inhalation hazards.  (c) Powerhouse - 6th floor - On or about January 6, 2020 and at times prior thereto, the exit routes throughout the 8th floor including, but not limited to: bay 9 through 16 were not clearly visible, this exposed employees to fire and smoke inhalation hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.37 B04

Serious Gravity 5 3 instances 100 exposed
Issued
May 13, 2020
Abate by
Jun 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent.  (a) Powerhouse - 8th floor (phase gallery) - On or about January 6, 2020 and at times prior thereto, signs were not posted throughout the 8th floor including, but not limited to: bay 9 through 16, this exposed employees to fire and smoke inhalation hazards.  (b) Powerhouse - 7th floor (cable gallery) - On or about January 6, 2020 and at times prior thereto, signs were not posted throughout the 7th floor including, but not limited to: bay 9 through 16 were not clearly visible, this exposed employees to fire and smoke inhalation hazards.  (c) Powerhouse - 6th floor - On or about January 6, 2020 and at times prior thereto, signs were not posted throughout the 8th floor including, but not limited to: bay 9 through 16 were not clearly visible, this exposed employees to fire and smoke inhalation hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.157 D02

Serious Gravity 1 2 instances 75 exposed
Issued
May 13, 2020
Abate by
Jun 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.157(d)(2): Portable fire extinguishers for use on Class A fires were not distributed so that the travel distance for employees to any extinguisher was 75 feet or less.  (a) Power House - 6th floor - Bay 16 - On or about January 6, 2020 and at times prior thereto, employees were exposed to fire and smoke inhalation hazards in that a portable fire extinguisher was approximately 125' of travel distance.  (b) Power House - 6th floor - Bay 12 - On or about January 6, 2020 and at times prior thereto, employees were exposed to fire and smoke inhalation hazards in that a portable fire extinguisher was more than approximately 114'' of travel distance.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.159 C02

Serious Gravity 5 1 instance 100 exposed
Issued
May 13, 2020
Abate by
Sep 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.159(c)(2): The employer did not properly maintain the installed automatic sprinkler system.  (a) Powerhouse - Station Service Transformer Vaults - TEMCO Fine Water Mist System - On or about January 6, 2020 and at times prior thereto, employees were exposed to fire, smoke and explosion hazard in that the fire suppression system was not properly maintained.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.164 C01

Serious Gravity 5 1 instance 100 exposed
Issued
May 13, 2020
Abate by
Sep 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.164(c)(1): The employer did not maintain all systems in an operable condition except during repairs or maintenance.  (a) Powerhouse - Control Room - On or about January 6, 2019 and at times prior thereto, the Very Early Detection (VESDA) System was not maintained in a operable condition in that the Siemens software was expired and no longer working. This prevented immediate identification of the location of alarms. Employees were exposed to fire and inhalation hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.164 C04

Serious Gravity 5 3 instances 100 exposed
Issued
May 13, 2020
Abate by
Sep 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.164(c)(4): The employer shall assure that the servicing, maintenance and testing of fire detection systems, including cleaning and necessary sensitivity adjustments are performed by a trained person knowledgeable in the operations and functions of the system.  (a) Powerhouse - Control Room - On or about January 6, 2019 and at times prior thereto, the servicing, maintenance and testing of the Very Early Smoke Detection (VESDA) system was not performed by a trained person knowledgeable in the operations and function of the system. This exposed employees to a system that may not work properly, which could result in fire and smoke inhalation.  (b) Powerhouse - Control Room - On or about January 6, 2019 and at times prior thereto, the servicing, maintenance and testing of the GE ESTxxx, which controls the elevators, was not performed by a trained person knowledgeable in the operations of the system.  (c) Powerhouse - 3rd floor - On or about January 6, 2019 and at times prior thereto, the servicing, maintenance and testing of the Fine Water Mist system.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.165 D02

Serious Gravity 5 100 instances 100 exposed
Issued
May 13, 2020
Abate by
Jun 30, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.165(d)(2): Tests of the reliability and adequacy of non-supervised employee alarm systems were not made at least every two months.  (a) The Dalles Dam - Powerhouse - On or about January 6, 2020 and at times prior thereto, employees were exposed to fire and smoke inhalation in that employees are working in remote locations, throughout the power house, without adequate emergency notification.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.269 L03 III

Serious Gravity 5 1 instance 1 exposed
Issued
May 13, 2020
Abate by
Jun 9, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.269(l)(3)(iii): The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance.  (a) Powerhouse - 5th floor - XJ Circuit Breaker Panel - On or about January 6, 2019 and at times prior thereto, an employee was exposed to contact with 125 Volt Direct Current (VDC) while applying a lock and tag in the circuit breaker panel.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

View Army Corps of Engineers's full OSHA safety record →