Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: O'RYAN OIL & GAS

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of O'RYAN OIL & GAS in 8061 NE CR 2100, POWELL, TX 75153 (NAICS 211112). OSHA activity number 344618905.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch O'Ryan OIL & GAS for free Get an email when a new federal OSHA severe-injury report for O'Ryan OIL & GAS is published. One employer, no account, unsubscribe in one click.
Establishment
O'RYAN OIL & GAS
Site address
8061 NE CR 2100
City
POWELL
State
TX
ZIP
75153
Mailing
1 MISSION BLVD., ODESSA, TX 79765
Inspection type
Follow-up (F)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
211112
Employees
18
Ownership type
Private (A)

6 citations on file for this inspection.

1910.38 E

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Jul 23, 2020
Abate by
Aug 20, 2020
Penalty
Initial $3,393 · Current $0 Reduced
29 CFR 1910.38(e): 29 CFR 1910.38(e):  The employer did not designate and train a sufficient number of persons to assist in the safe and orderly emergency evacuation of employees.   On or about February 7, 2020, and times prior thereto, the employer did not train employees on the emergency action plan exposing employees to fire and explosion hazards.
Recent events (3)
  • · R (S) $0
  • · C (S) $3393
  • · Z (S) $3393

1910.119 E01

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Jul 23, 2020
Abate by
Aug 31, 2020
Penalty
Initial $5,937 · Current $0 Reduced
29 CFR 1910.119(e)(1): The process hazard analysis was not appropriate to the complexity of the process and did not identify, evaluate, and control the hazards involved in the process:   On or about February 7, 2020 and at times prior thereto at the Big R Gas Plant in Powell, Texas, when the employers PHA did not to identify, evaluate, and control the hazards associated with the flare and knockout system. This condition exposed workers to hazards including but not limited to fire, explosion, and inhalation of hazardous materials.
Recent events (3)
  • · R (S) $0
  • · C (S) $5937
  • · Z (S) $5937

1910.119 E05

Deleted Serious Gravity 10 3 instances 4 exposed
Issued
Jul 23, 2020
Abate by
Aug 31, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.119(e)(5): The employer did not establish a system to assure that required action items from the process hazard analysis (PHA) were resolved in a timely manner and that the resolutions were documented..  On or about February 7, 2020, and times prior thereto, at the Big R Gas Plant in Powell, Texas, the employer did not implement required action items from the 2010 process hazard analysis to evaluate and control the associated hazards of the process, exposing workers to fire, explosion and inhalation hazards.   (a) The employer did not implement the action item from the 2010 hazard assessment to perform PHA of the HP and LP flare systems. (b)  The employer did not implement the action item from the 2010 hazard assessment to perform PHA of the Inlet Compression System. (c) The employer did not implement the action item from the 2010 hazard assessment to perform PHA of the Sales Gas Compression System
Recent events (3)
  • · R (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.119 E06

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Jul 23, 2020
Abate by
Aug 31, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.119(e)(6): The process hazard analysis was not revalidated at least every five years to assure its consistency with the current process:  On or about February 7, 2020 at the Big R Gas Plant in Powell, Texas, the employer did not ensure that the process hazard analysis for the process was revalidated at least every five years to assure it represents the current process and that hazards continue to be identified, evaluated, and measures taken to mitigate the identified hazards.
Recent events (3)
  • · R (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.119 J02

Deleted Repeat Gravity 10 1 instance 5 exposed
Issued
Jul 23, 2020
Abate by
Aug 31, 2020
Penalty
Initial $11,875 · Current $0 Reduced
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment.   On or about February 7, 2020, and times prior thereto, at the Big R Gas Plant in Powell, Texas,  the employer did not establish and implement written procedures to maintain the on-going integrity of the Flare System.  O'Ryan Oil & Gas was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.119(j)(2), which was contained in OSHA inspection number 1357199, citation number 01, item number 7/a and was affirmed as a final order on April 22, 2019, with respect to a workplace located at 8601 NE CR 2100, Powell, Texas 75153.
Recent events (3)
  • · R (R) $0
  • · C (R) $11875
  • · Z (R) $11875

1910.119 J05

Deleted Repeat Gravity 10 1 instance 4 exposed
Issued
Jul 23, 2020
Abate by
Aug 31, 2020
Penalty
Initial $11,875 · Current $0 Reduced
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) in a safe and timely manner and did not ensure that means were taken in the interim to assure safe operation.  On or about February 7, 2020, and times prior thereto, at the Big R Gas Plant in Powell, Texas, the employer did not correct deficiencies in flare system that caused the flare igniter not to function and did not implement interim measures to ensure safety of the process.  O'Ryan Oil & Gas was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.119(j)(5), which was contained in OSHA inspection number 1357199, citation number 01, item number 8/b and was affirmed as a final order on April 22, 2019), with respect to a workplace located at 8601 NE CR 2100, Powell, Texas 75153.
Recent events (3)
  • · R (R) $0
  • · C (R) $11875
  • · Z (R) $11875

View O'Ryan OIL & GAS's full OSHA safety record →