Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CUSTOM FABRICATORS, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CUSTOM FABRICATORS, INC. in 1900 14TH AVENUE NORTHWEST, WATERTOWN, SD 57201 (NAICS 332999). OSHA activity number 344621883.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Custom Fabricators, INC. — free Get an email when a new federal OSHA severe-injury report for Custom Fabricators, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1900 14TH AVENUE NORTHWEST
City
WATERTOWN
State
SD
ZIP
57201
Mailing
1900 14TH AVENUE NORTHWEST, WATERTOWN, SD 57201
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332999
Employees
85
Ownership type
A

11 citations on file for this inspection.

1910.134 C01

Serious Gravity 1 1 instance 1 exposed
Issued
Jun 11, 2020
Abate by
Jan 4, 2021
Penalty
Initial $3,441 · Current $2,300 Reduced
29 CFR 1910.134(c)(1): A written respiratory protection program that included the provisions in 29 CFR 1910.134(c)(1)(i) - (ix) with worksite specific procedures was not established and implemented for required respirator use:    (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that employees were protected from chemical hazards and hazards associated with respirator use in that, the company had not established and implemented a written respiratory protection program covering employee use of respirators. This condition exposed employees to chemical hazards and hazards associated with respirator use.    Abatement Note:  The following provisions of this section include:  (i) Procedures for selecting respirators in the workplace;  (ii) Medical evaluations of employees required to use respirators;  (iii) Fit-testing procedures for tight-fitting respirators;   (iv) Procedures for proper use of respirators in routine and reasonably foreseeable emergency situations;  (v) Procedures and schedules for cleaning, disinfecting, storing, inspecting, repairing, discarding, and otherwise maintaining respirators;  (vi) Procedures to ensure adequate air quality, quantity, and flow of breathing air for atmosphere-supplying respirators;  (vii) Training of employees in the respiratory hazards to which they are potentially exposed during routine and emergency situations.  (viii) Training of employees in the proper use of respirators, including putting on and removing them, any limitations on their use, and the maintenance; and  (ix) Procedures for regularly evaluating the effectiveness of the program
Recent events (4)
  • — P (S) $2300
  • — P (S) $2300
  • — I (S) $2300

1910.303 F02

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $3,441 · Current $1,700 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that employees were protected from electrical hazards in that, the 70-amp breaker installed in Panel #5 of the Main Welding Shop for use with the Tru-Weld SC1900 stud welder was not labeled as to its purpose. This condition exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $3441

1910.303 G01

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that employees were protected from electrical hazards in that, adequate working space was not maintained around the 110 volt electrical panel near the supervisor's office in the South Welding Shop, Building #2. This condition exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $4,588 · Current $2,500 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety related work practices required by 29 CFR 1910.331 through 29 CFR 1910.335 that pertained to their respective job assignments:      (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure employees were trained and familiar with electrical safety related work practices to include the risk of injury associated with installing a 70-amp breaker in an energized electrical panel. The employer did not develop practices and train employees to prevent electric shock or other injuries when work is performed near or on equipment or circuits which are or may be energized. This condition exposed employees to hazards such as burns, shock, electrocution, arc blast, and arc flash.      Abatement Note: Training requirements are found in 29 CFR 1910.331 through 29 CFR 1010.335. The training required by this section shall be of the classroom or on-the-job type. The degree of training provided shall be determined by the risk to the employee.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4588

1910.333 A

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a): Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards:  (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that each employee was provided with appropriate safe work practices to be employed to prevent shock or other injuries resulting from either direct or indirect electrical contact and the use of the necessary electrical protective equipment. An employee installing a 70-amp breaker in Panel #5, turned off the panel's main breaker but did not de-energize the panel prior to installing the breaker. The employee was exposed to live electrical components associated with working within Panel #5 when removing the dead front cover to install the breaker. This condition exposed employees to burns, shock, and electrocution hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A01

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that each employee working on or near live electrical components de-energized prior to beginning work. An employee installing a 70-amp breaker in Panel #5, turned off the panel's main breaker but did not de-energize the panel prior to installing the breaker. The employee was exposed to live electrical associated with working within Panel #5 when removing the dead front cover to install the breaker. This condition exposed employees to burns, shock, and electrocution hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(i): The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives. The written procedures may be in the form of a copy of paragraph (b) of this section:  (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that employees were protected from hazards associated with working on or near energized parts in that, the company had not developed a written copy of energy control procedures. This condition exposed employees to shock, burns and electrocution hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 11, 2020
Abate by
Jul 8, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2): While the employee is exposed to contact with live parts of fixed electrical equipment or circuits which have been de-energized, the circuits energizing the parts were not locked out or tagged out or both in accordance with the requirement in this paragraph:  (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that each employee locked out the circuits energizing the parts the employee was working on or near. An employee installing a 70-amp breaker in Panel #5, did not de-energize the panel and lock it out. This condition exposed employees to burns, shock, and electrocution hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Other-than-serious 1 instance 7 exposed
Issued
Jun 11, 2020
Abate by
Oct 1, 2020
Penalty
Initial $3,441 · Current $2,000 Reduced
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about, and at times prior to February 11, 2020, the employer did not ensure employees were protected from chemical hazards in that, the employer did not maintain their hazard communication program by, among other actions, provide training to employees prior to performing work with or in the vicinity of hazardous chemicals, update references of MSDS to the global harmonized system, and maintain a list of hazardous chemicals located at the facility. This condition exposed employees to chemical hazards.
Recent events (3)
  • — P (O) $2000
  • — I (O) $2000
  • — Z (S) $3441

1910.1026 L01 III

Serious Gravity 1 1 instance 1 exposed
Issued
Jun 11, 2020
Abate by
Oct 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.1026(l)(1)(iii): The employer had not included chromium (VI) in the hazard communication program, established to comply with the Hazard Communication Standard, 29 CFR 1910.1200:    (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not ensure that one employee was protected from hazards associated with exposure to hexavalent chromium in that the company's hazard communication program did not include hexavalent chromium. This condition exposed employees to hazards related to exposure to hexavalent chromium.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1026 D01

Other-than-serious 1 instance 1 exposed
Issued
Jun 11, 2020
Abate by
Jan 4, 2021
Penalty
Initial $0 · Current $0
29 CFR 1910.1026(d)(1): The employer with a workplace or work operation covered by this standard did not determine the 8-hour time-weighted average exposure for each employee exposed to chromium (VI):    (a)Custom Fabricators, Inc. at 1900 14th Avenue Northwest, Watertown, SD 57201: On or about and at times prior to February 11, 2020, the employer did not determine the average 8-hour time-weighted average exposure to hexavalent chromium for employees performing welding and/or grinding on stainless steel and employees performing surface welding on Rock Bodies with chromium containing compounds. This condition exposed employees to respiratory hazards.
Recent events (3)
  • — P (O) $0
  • — I (O) $0
  • — Z (O) $0

View Custom Fabricators, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344621883.