Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: RUN ENERGY MANAGEMENT, L.L.C.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of RUN ENERGY MANAGEMENT, L.L.C. in 4092 COUNTY ROAD 140, SEYMOUR, TX 76380 (NAICS 221115). OSHA activity number 344784731.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RUN Energy Management, L.L.C. for free Get an email when a new federal OSHA severe-injury report for RUN Energy Management, L.L.C. is published. One employer, no account, unsubscribe in one click.
Site address
4092 COUNTY ROAD 140
City
SEYMOUR
State
TX
ZIP
76380
Mailing
5009 SOUTH DANVILLE DR., ABILENE, TX 79602
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221115
Employees
260
Ownership type
A

6 citations on file for this inspection.

1910.269 A02 II D

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jul 14, 2020
Abate by
Aug 11, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1910.269(a)(2)(ii)(D): The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment.   At a work place located at 4092 County Road 140, Seymour, Texas; an employee worked on an energized cabinet of 12,000 volts and was not protected from flash arc burn injuries.  The employer did not ensured the employee use the protective equipment exposing him to the hazards of arc flash burns.
Recent events (2)
  • · I (S) $0
  • · Z (S) $13494

1910.269 A02 IV

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jul 14, 2020
Abate by
Aug 11, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(2)(iv): The employer did not determine that each employee is complying with all required safety related work practices by regular supervision and Annual inspections.     At a work place located at 4092 County Road 140, Seymour, Texas; the employer did not ensured that employees working on an energized panel at the base of the wind turbine, treat them as being energized, exposing them to arc flash hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.269 L01 III

Other-than-serious 1 instance 3 exposed
Issued
Jul 14, 2020
Abate by
Aug 30, 2020
Penalty
Initial $7,711 · Current $12,000
29 CFR 1910.269(l)(1)(iii): Electric lines and equipment were not considered and treated as energized before they had been deenergized in accordance with paragraph (d) or (m) of this section.      At a work place located at 4092 County Road 140, Seymour, Texas; the employer did not ensured, employees working on or near energized switch gears, treat them as being energized, exposing them to arc flash hazards.
Recent events (2)
  • · I (O) $12000
  • · Z (S) $7711

1910.269 L03 III

Other-than-serious 1 instance 3 exposed
Issued
Jul 14, 2020
Abate by
Aug 30, 2020
Penalty
Initial $0 · Current $12,000
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:       At a work place located at 4092 County Road 140, Seymour, Texas; the employer did not ensured, an employee working within the minimum approach distant, did not placed a conductive object in or near energized parts.  The employee was exposed to arc flash hazards.
Recent events (2)
  • · I (O) $12000
  • · Z (S) $0

1910.269 L08 III

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Jul 14, 2020
Abate by
Aug 11, 2020
Penalty
Initial $5,783 · Current $0 Reduced
29 CFR 1910.269(l)(8)(iii):The employer failed to ensure that each employee exposed to electric arc hazards wears protective clothing with a arc rating designed to provide the necessary protection.   At a work place located at 4092 County Road 140, Seymour, Texas; the employer did not ensured the employee wear protective clothing while working on energized equipment.  The employee was  exposed to arc flash hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $5783

1904.39 A02

Deleted Other-than-serious 1 instance 1 exposed
Issued
Jul 14, 2020
Abate by
Aug 11, 2020
Penalty
Initial $9,639 · Current $0 Reduced
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye.   At a work place located at 4092 County Road 140, Seymour, Texas; an employee sustained arc flash burns while working on an energized cabinet of 12,000 volts.  The employer did not report the accident to the Occupational Safety and Health Administration within 24 hours.
Recent events (2)
  • · I (O) $0
  • · Z (O) $9639

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344784731.