Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: STANDARD CONCRETE PRODUCTS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of STANDARD CONCRETE PRODUCTS, INC. in 5801 COMMERCE ST., TAMPA, FL 33616 (NAICS 327390). OSHA activity number 344885173.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Standard Concrete Products, INC. — free Get an email when a new federal OSHA severe-injury report for Standard Concrete Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
5801 COMMERCE ST.
City
TAMPA
State
FL
ZIP
33616
Mailing
P.O. BOX 1360, COLUMBUS, GA 31902
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327390
Employees
120
Ownership type
A

2 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 3 instances 5 exposed
Issued
Dec 3, 2020
Penalty
Initial $7,711 · Current $4,627 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a) On or about 08/17/2020, by the concrete form area, a 110VAC plug box used by employees was not effectively secured to its mount resulting in an opening/gap where its inner wiring was exposed to the elements. A metal wire had also been wrapped inside the exposed opening/gap and protruded out of the opening/gap. This condition exposed employees to electric shock hazards.  b) On or about 08/17/2020, by the concrete form area, a 110VAC breaker box had a 7/16 inch opening next to an electrical plug exposing its inner wiring to the elements. This condition exposed employees to electrical shock hazards.  c) On or about 08/17/2020, by the concrete form area, multiple 110VAC electrical boxes had unused, open knockouts on the bottom side of the boxes exposing inner wiring to the elements. This condition exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $4626.6
  • — Z (S) $7711

1910.305 B01 I

Other-than-serious 1 instance 5 exposed
Issued
Dec 3, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:  a) On or about 08/17/2020, as observed at the concrete form area, conduit entering an electrical box was not fitted to the electrical box resulting in potential abrasion to the internal wiring.