Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RECREATION UNLIMITED, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of RECREATION UNLIMITED, LLC in 111 MATTHEWS DRIVE, AMERICUS, GA 31709 (NAICS 336612). OSHA activity number 344951041.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Recreation Unlimited, LLC — free Get an email when a new federal OSHA severe-injury report for Recreation Unlimited, LLC is published. One employer, no account, unsubscribe in one click.
Site address
111 MATTHEWS DRIVE
City
AMERICUS
State
GA
ZIP
31709
Mailing
111 MATTHEWS DRIVE, AMERICUS, GA 31709
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336612
Employees
102
Ownership type
A

7 citations on file for this inspection.

1910.28 B01 I

Serious Gravity 1 1 instance 7 exposed
Issued
Mar 17, 2021
Abate by
Apr 12, 2021
Penalty
Initial $5,792 · Current $3,475 Reduced
29 CFR  1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the following: guardrail systems, safety net systems, or personal fall protection systems, such as personal fall arrest, travel restraint, or positioning systems.  a). Building 1 (Main Facility), Frame Assembly & Final Finish - On or about and times prior to September 29, 2020, a fall protection system was not provided to employees working from the deck of the pontoon boats, thus exposing employees to a fall hazard of approximately 4 feet 4 inches.
Recent events (2)
  • — I (S) $3475.2
  • — Z (S) $5792

1910.106 E02 II B 2

Serious Gravity 10 1 instance 16 exposed
Issued
Mar 17, 2021
Penalty
Initial $13,516 · Current $8,110 Reduced
29 CFR  1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons.  a). Lamination Department - On or about and times prior to September 29, 2020, approximately 700 gallons of Category 3 flammable liquids (i.e. gel coat) were stored outside of an inside storage room or cabinet, thus exposing employees to a fire hazard.
Recent events (2)
  • — I (S) $8109.6
  • — Z (S) $13516

1910.303 F02

Serious Gravity 5 2 instances 5 exposed
Issued
Mar 17, 2021
Penalty
Initial $11,586 · Current $6,952 Reduced
29 CFR  1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.   a). Building # 1 (Main Facility), Finial Finish - On or about and times prior to September 29, 2020, there was an electrical circuit breaker box that had several individual circuit breakers that were not marked with their intended purpose, thus exposing employees to electrical and fire hazards.   b). Building # 2 (Trailer Fabrication) - On or about and times prior to September 29, 2020, there was an electrical circuit breaker box that had several individual circuit breakers that were not marked with their intended purpose, thus exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $6951.6
  • — Z (S) $11586

1910.303 G02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Mar 17, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a).  Building # 2 (Trailer Fabrication) - On or about and times prior to September 29, 2020, live electrical conductors inside an wireway box was not guarded to prevent accidental contract, thus exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 2 instances 5 exposed
Issued
Mar 17, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  a). Building # 1 (Main Facility), Finial Finish - On or about and times prior to September 29, 2020, there was an unused opening inside an electrical breaker box that was not effectively closed, thus exposing employees to electrical and fire hazards.  b). Building # 2 (Trailer Fabrication) - On or about and times prior to September 29, 2020, there were unused openings inside two electrical breaker boxes that were not effectively closed, thus exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 A04

Other-than-serious 1 instance 15 exposed
Issued
Mar 17, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.178(a)(4): Modifications and additions which affect capacity and safe operation of powered industrial truck were performed by the employer without the manufacturer's prior written approval.  a). Building # 2 (Trailer Fabrication) and Building # 4 (Paint Shop) - On or about and times prior to September 29, 2020, the employer did not obtain written manufacturer's approval for tow attachments used on a Nissan forklift (model: 40) and a Daewoo forklift, thus exposing employees to a struck-by hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 L05

Other-than-serious 1 instance 15 exposed
Issued
Mar 17, 2021
Abate by
Apr 12, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.178(l)(5): The employer did not evaluate the competency of the operator who had previously received training appropriate to the truck and working conditions encountered.    a). At the workplace - On or about and times prior to September 29, 2020, the employer did not evaluate the competency of employees that operated forklifts (e.g. Taylor, Lift Master, Nissan, Daewoo), thus exposing employees to a programmatic hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Recreation Unlimited, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344951041.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.