GALENA PARK, TX —
OSHA Inspection: KINDER MORGAN, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of KINDER MORGAN, INC. in 407 CLINTON DR., GALENA PARK, TX 77547 (NAICS 324110). OSHA activity number 344989728.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KINDER MORGAN, INC.
- Site address
- 407 CLINTON DR.
- City
- GALENA PARK
- State
- TX
- ZIP
- 77547
- Mailing
- 407 CLINTON DR., GALENA PARK, TX 77547
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 36
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 D03 I H
- Issued
- Mar 25, 2021
- Abate by
- Apr 13, 2021
- Penalty
- Initial $8,953 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(H): Process safety information pertaining to the equipment in the process did not include the safety systems (e.g., interlocks, detection or suppression systems On or about October 23, 2020, at Kinder Morgan Crude & Condensate Plant, process safety information was not included for safety systems including but not limited to: a) Combi tower T-102: PAHH - 11715 b) Combi Tower Accumulator PV-102: LALL - 11325 c) Ultima XE MSA detector at Splitter 1 A14-4507465-10-001 d) Ultima XE MSA detector at Splitter 1 A14-4507465-10-003 e) Ultima XE MSA detector at Splitter1 A14-4507465-10-004 f) Ultima XE MSA detector at Splitter 1 A14-4507465-10-005 g) Ultima XE MSA detector at Splitter 1 A14-4507465-10-002 (40AT-10416) h) Ultima XE MSA detector at Splitter 1 A14-4507465-10-006 (40AT-10441)
Recent events (2)
- — I (S) $0
- — Z (S) $8953
1910.119 D03 II
- Issued
- Mar 25, 2021
- Abate by
- Apr 15, 2021
- Penalty
- Initial $8,953 · Current $6,715 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii):The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP): On or about October 23, 2020, at the at Kinder Morgan Crude & Condensate Park Splitter located in Galena Park, the employer did not document and audit mechanical locking devices on isolation valves used upstream and downstream of pressure relieving devices to verify they remained in the desired position through management practices outlined in ASME Section VIII, Appendix M and Kinder Morgan Procedure No. AP-0917.
Recent events (2)
- — I (S) $6715
- — Z (S) $8953
1910.119 J02
- Issued
- Mar 25, 2021
- Abate by
- Apr 13, 2021
- Penalty
- Initial $12,288 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment. On or about October 23, 2020, at Kinder Morgan Crude & Condensate Plant located in Galena Park, Texas, the employer did not implement written procedures to maintain the on-going integrity of process equipment. Including, but not limited to: a) COMBI TOWER T-102: PAH - 11271 b) Combi Tower Accumulator PV-102: FALL - 11350 (Tag FT-11350) c) Combi Tower Accumulator PV-102: LALL - 11325 (Tag LT-11325) d) Naphtha Stabilizer Accumulator PV-101: LAH - 10360
Recent events (2)
- — I (S) $0
- — Z (S) $12288
1910.119 J04 I
- Issued
- Mar 25, 2021
- Abate by
- May 3, 2021
- Penalty
- Initial $12,288 · Current $12,288
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment On or about October 23, 2020, at Kinder Morgan Crude & Condensate Plant located in Galena Park, Texas, the employer did not perform inspections and tests on process equipment. Including, but not limited to: a) COMBI TOWER T-102: PAH - 11271 b) Combi Tower Accumulator PV-102: FALL - 11350 (Tag FT-11350) c) Combi Tower Accumulator PV-102: LALL - 11325 (Tag LT-11325) d) Naphtha Stabilizer Accumulator PV-101: LAH - 10360
Recent events (2)
- — I (S) $12288
- — Z (S) $12288
More inspections at Kinder Morgan, INC.