Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KINDER MORGAN, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of KINDER MORGAN, INC. in 407 CLINTON DR., GALENA PARK, TX 77547 (NAICS 324110). OSHA activity number 344989728.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kinder Morgan, INC. — free Get an email when a new federal OSHA severe-injury report for Kinder Morgan, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
KINDER MORGAN, INC.
Site address
407 CLINTON DR.
City
GALENA PARK
State
TX
ZIP
77547
Mailing
407 CLINTON DR., GALENA PARK, TX 77547
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
Employees
36
Ownership type
A

4 citations on file for this inspection.

1910.119 D03 I H

Deleted Serious Gravity 5 8 instances 6 exposed
Issued
Mar 25, 2021
Abate by
Apr 13, 2021
Penalty
Initial $8,953 · Current $0 Reduced
29 CFR  1910.119(d)(3)(i)(H): Process safety information pertaining to the equipment in the process did not include the safety systems (e.g., interlocks, detection or suppression systems  On or about October 23, 2020, at Kinder Morgan Crude & Condensate Plant, process safety information was not included for safety systems including but not limited to:  a) Combi tower T-102: PAHH - 11715  b) Combi Tower Accumulator PV-102: LALL - 11325 c) Ultima XE MSA detector at Splitter 1 A14-4507465-10-001 d) Ultima XE MSA detector at Splitter 1 A14-4507465-10-003 e) Ultima XE MSA detector at Splitter1 A14-4507465-10-004 f) Ultima XE MSA detector at Splitter 1 A14-4507465-10-005  g) Ultima XE MSA detector at Splitter 1 A14-4507465-10-002 (40AT-10416) h) Ultima XE MSA detector at Splitter 1 A14-4507465-10-006 (40AT-10441)
Recent events (2)
  • — I (S) $0
  • — Z (S) $8953

1910.119 D03 II

Serious Gravity 5 1 instance 6 exposed
Issued
Mar 25, 2021
Abate by
Apr 15, 2021
Penalty
Initial $8,953 · Current $6,715 Reduced
29 CFR 1910.119(d)(3)(ii):The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP):  On or about October 23, 2020, at the at Kinder Morgan Crude & Condensate Park Splitter located in Galena Park, the employer did not document and audit mechanical locking devices on isolation valves used upstream and downstream of pressure relieving devices to verify they remained in the desired position through management practices outlined in ASME Section VIII, Appendix M and Kinder Morgan Procedure No. AP-0917.
Recent events (2)
  • — I (S) $6715
  • — Z (S) $8953

1910.119 J02

Deleted Serious Gravity 10 4 instances 6 exposed
Issued
Mar 25, 2021
Abate by
Apr 13, 2021
Penalty
Initial $12,288 · Current $0 Reduced
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment.   On or about October 23, 2020, at Kinder Morgan Crude & Condensate Plant located in Galena Park, Texas, the employer did not implement written procedures to maintain the on-going integrity of process equipment. Including, but not limited to:  a) COMBI TOWER T-102: PAH - 11271  b) Combi Tower Accumulator PV-102: FALL - 11350 (Tag FT-11350) c) Combi Tower Accumulator PV-102: LALL - 11325 (Tag LT-11325) d) Naphtha Stabilizer Accumulator PV-101: LAH - 10360
Recent events (2)
  • — I (S) $0
  • — Z (S) $12288

1910.119 J04 I

Serious Gravity 10 4 instances 6 exposed
Issued
Mar 25, 2021
Abate by
May 3, 2021
Penalty
Initial $12,288 · Current $12,288
29 CFR  1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment   On or about October 23, 2020, at Kinder Morgan Crude & Condensate Plant located in Galena Park, Texas, the employer did not perform inspections and tests on process equipment. Including, but not limited to:  a) COMBI TOWER T-102: PAH - 11271  b) Combi Tower Accumulator PV-102: FALL - 11350 (Tag FT-11350) c) Combi Tower Accumulator PV-102: LALL - 11325 (Tag LT-11325) d) Naphtha Stabilizer Accumulator PV-101: LAH - 10360
Recent events (2)
  • — I (S) $12288
  • — Z (S) $12288

View Kinder Morgan, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344989728.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.