Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MFH ENVIRONMENTAL, CORP.

Programmed Related inspection · Health discipline

On , OSHA opened a programmed Related health inspection of MFH ENVIRONMENTAL, CORP. in 421 MANGRUM CR, EL PASO, TX 79912 (NAICS 238910). OSHA activity number 345117378.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MFH Environmental, Corp. — free Get an email when a new federal OSHA severe-injury report for MFH Environmental, Corp. is published. One employer, no account, unsubscribe in one click.
Site address
421 MANGRUM CR
City
EL PASO
State
TX
ZIP
79912
Mailing
1932 W. PAISANO DR., EL PASO, TX 79922
Inspection type
Programmed Related (J)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238910
Employees
32
Ownership type
A

5 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 4 instances 21 exposed
Issued
Apr 5, 2021
Abate by
Apr 16, 2021
Penalty
Initial $5,266 · Current $2,600 Reduced
29 CFR  1926.403(b)(2):Installation and use. Listed, labeled, or certified equipment shall be installed and used in accordance with instructions included in the listing, labeling, or certification.  On or about January 26. 2021, the Force Air 2000 EC air exhaust units were connected using more than one power extension cords connected together (Daisy chain connection) that were not installed in accordance to the manufacture's listed label use.  This condition exposed employees to electrical shock and /or burns.
Recent events (2)
  • — I (S) $2600
  • — Z (S) $5266

1926.404 B01 III

Serious Gravity 5 2 instances 12 exposed
Issued
Apr 5, 2021
Abate by
Apr 16, 2021
Penalty
Initial $0 · Current $0
29 CFR  1926.404(b)(1)(iii): Assured equipment grounding conductor program. The employer shall establish and implement an assured equipment grounding conductor program on construction sites covering all cord sets, receptacles which are not a part of the building or structure, and equipment connected by cord and plug which are available for use or used by employees.    On or about January 26. 2021, an equipment grounding conductor program  was not developed and implemented at the construction jobsite that covers all flexible cord sets that connect the Force Air 2000 EC air exhaust units being used. This condition exposed employees to electrical shock and /or burns.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G02 IV

Serious Gravity 5 3 instances 12 exposed
Issued
Apr 5, 2021
Abate by
Apr 16, 2021
Penalty
Initial $0 · Current $0
29 CFR  1926.405(g)(2)(iv): Strain relief. Flexible cords shall be connected to devices and fittings so that strain relief is provided which will prevent pull from being directly transmitted to joints or terminal screws.   On or about January 26. 2021, the Force Air 2000 EC air exhaust units were connected using power extension cords without strain relief or strain relief that was damaged.   This condition exposed employees to electrical shock and /or burns.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Other-than-serious 4 instances 12 exposed
Issued
Apr 5, 2021
Abate by
Apr 16, 2021
Penalty
Initial $986 · Current $500 Reduced
29 CFR  1926.405(b)(1): Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed.  On or about January 26. 2021, electrical cabinet labeled no.8  on portable power control board had unused openings that were not cover or effectively closed.   This condition exposed employees to electrical shock and /or burns.
Recent events (2)
  • — I (O) $500
  • — Z (O) $986

1926.405 B02

Other-than-serious 4 instances 12 exposed
Issued
Apr 5, 2021
Abate by
Apr 16, 2021
Penalty
Initial $986 · Current $500 Reduced
29 CFR  1926.405(b)(2):All pull boxes, junction boxes, or fittings were not provided with covers and in energized installations each outlet box did not have a cover, faceplate, or fixture canopy.  On or about January 26. 2021, electrical outlet box were not provided with a cover plate.   This condition exposed employees to electrical shock and /or burns.