VERNON, CT —
OSHA Inspection: ALDI INC. (CONNECTICUT)
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ALDI INC. (CONNECTICUT) in 360 TALCOTTVILLE ROAD, VERNON, CT 06066 (NAICS 445110). OSHA activity number 345135818.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALDI INC. (CONNECTICUT)
- Site address
- 360 TALCOTTVILLE ROAD
- City
- VERNON
- State
- CT
- ZIP
- 06066
- Mailing
- 295 RYE STREET, SOUTH WINDSOR, CT 06074
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 30
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.304 F01 IV
- Issued
- Apr 8, 2021
- Penalty
- Initial $3,730 · Current $2,250 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: Sprinkler Room: On, or about, January 25, 2021, items such as a ladder, tote, boxes and a floor cleaner were stored in front of a GE Spectra Series panelboard and a Siemens PowerWall panelboard, limiting access to the overcurrent devices.
Recent events (2)
- — I (S) $2250
- — Z (S) $3730
1910.305 G01 IV A
- Issued
- Apr 8, 2021
- Penalty
- Initial $4,974 · Current $2,250 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: A. Sprinkler Room: On, or about, January 25, 2021, a green extension cord was used to charge the Tennant floor cleaner. B. Back Room: On, or about, January 25, 2021, an orange extension cord was used to charge a Raymond pallet jack.
Recent events (2)
- — I (O) $2250
- — Z (S) $4974
1910.334 A02 II
- Issued
- Apr 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service: Back Room: On, or about, January 25, 2021, flexible cords were damaged: A. Orange extension cord used to energize the Raymond pallet jack was damaged in three locations, exposing the inner coated conductors. B. Black charging cord provided for the middle Raymond pallet jack had a crushed/split male end, exposing the inner components. C. Black charging cord provided for the right Raymond pallet jack had a split out jacket, exposing the inner coated conductors.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Apr 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment: Back Room: On, or about, January 25, 2021, electrical conduit that contained two receptacles boxes was pulled from the wall and was no longer supported.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.304 B04 II B
- Issued
- Apr 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4: Breakroom: On, or about, January 25, 2021, a GE microwave oven and a Cuisinart toaster oven were energized through the same wall receptacle. The combined load on the receptacle was 17.8 amperes, which exceeded the maximum load allowed of 16 amperes.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B02 I
- Issued
- Apr 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Office: On, or about, January 25, 2021, a wall mounted receptacle located under the Main Computer desk was not provided with a faceplate.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Aldi INC. (Connecticut)
View Aldi INC. (Connecticut)'s full OSHA safety record →
More inspections in this industry (NAICS 445110)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345135818.