OSHA Inspection: MAZATZAL HOTEL & CASINO

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of MAZATZAL HOTEL & CASINO in HWY 87 MILEPOST 25, PAYSON, AZ 85541 (NAICS 721120). OSHA activity number 345148100.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mazatzal Hotel & Casino — free Get an email when a new federal OSHA severe-injury report for Mazatzal Hotel & Casino is published. One employer, no account, unsubscribe in one click.
Site address
HWY 87 MILEPOST 25
City
PAYSON
State
AZ
ZIP
85541
Mailing
P.O. BOX 1820, PAYSON, AZ 85547
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
200
Ownership type
A

5 citations on file for this inspection.

1910.151 C

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 14, 2021
Penalty
Initial $7,461 · Current $3,727 Reduced
29 CFR  1910.151(c):Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  a)	WAREHOUSE- Employees who charged and refilled the battery on the Nissan 35 Forklift S/N 1N11 18V were exposed to corrosives battery acids and did not have access to an eyewash.
Recent events (2)
  • — I (S) $3726.5
  • — Z (S) $7461

1910.303 B02

Serious Gravity 5 5 instances 13 exposed
Issued
Apr 14, 2021
Penalty
Initial $8,953 · Current $4,500 Reduced
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a)	SHOP 3-Two metal receptacle boxes powered by a flexible cord and plug were "daisy chained", where the first metal receptacle box was plugged into a second metal receptacle box, exposing employees to electrical shock hazards. b)	HOUSEKEEPING OFFICE- A 15A relocatable power tap was supplying power to a microwave (14A), a computer workstation and printer, exposing employees to electrical shock hazards and burns.  c)	HOUSEKEEPING OFFICE- A relocatable power tap was "daisy chained" and supplying power to an extension cord and second relocatable power tap, exposing employees to electrical shock hazards.  d)	LAUNDRY ROOM- A relocatable power tap was mounted to a wall and supplying power to the ProClean automatic detergent dispensing system, exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $4500
  • — Z (S) $8953

1910.305 G01 IV A

Serious Gravity 5 1 instance 5 exposed
Issued
Apr 14, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) HOUSEKEEPING OFFICE- A microwave was powered by an extension cord and relocatable power tap, exposing employees to shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A03 II

Serious Gravity 5 1 instance 5 exposed
Issued
Apr 14, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.334(a)(3)(ii):Attachment plugs and receptacles were connected or altered in a manner which prevented proper continuity of the electric equipment grounding conductor at the point where plugs were attached to receptacles:  HOUSEKEEPING OFFICE- A microwave with a 3-prong cord was plugged into a 2-prong extension cord by use of a 3-prong-to-2 prong adaptor, bypassing the ground and exposing employees to shocks.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J02 I

Serious Gravity 5 2 instances 8 exposed
Issued
Apr 14, 2021
Penalty
Initial $5,969 · Current $5,969
29 CFR  1910.305(j)(2)(i):Receptacles were not installed so that an energized attachment plug was not its source of supply:  a)	SHOP 3:  A metal 4 outlet receptacle box mounted to the workbench was powered by a flexible cord with plug attachments, exposing employees to shock hazards.   b)	SHOP 3:   A metal 2 outlet receptacle box mounted to the workbench was powered by a flexible cord with plug attachments, exposing employees to shock hazards.
Recent events (2)
  • — I (S) $5969
  • — Z (S) $5969

View Mazatzal Hotel & Casino's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345148100.