EL DORADO, AR —
OSHA Inspection: DELEK US
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of DELEK US in 1000 MCHENRY AVE., EL DORADO, AR 71730 (NAICS 324110). OSHA activity number 345169197.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DELEK US
- Site address
- 1000 MCHENRY AVE.
- City
- EL DORADO
- State
- AR
- ZIP
- 71730
- Mailing
- P. O. BOX 7005, EL DORADO, AR 71730
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 290
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.119 F04
- Issued
- Aug 26, 2021
- Abate by
- Mar 15, 2022
- Penalty
- Initial $13,653 · Current $13,653
General-duty citation text
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel: On or about February 27, 2021, at the Lion Oil Refinery in El Dorado, AR workers were exposed to process hazards when the host employer did not implement safe work practices to prohibit the use of heavy equipment in a roadway with temporary naphtha piping.
Recent events (3)
- — F (S) $13653
- — C (S) $13653
- — Z (S) $13653
1910.119 H02 II
- Issued
- Aug 26, 2021
- Abate by
- Sep 30, 2021
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(h)(2)(ii):The employer did not inform contract employers of the known potential fire, explosion, or toxic release hazards related to the contractor's work and the process: On or about February 27, 2021 in the process area that includes Unit 6 and Unit 9 of the Lion Oil Refinery in El Dorado, AR, workers were exposed to fire, explosion and toxic release hazards when the employer did not inform contract employers that temporary piping in the roadway between the units connected process units and contained flammable hydrocarbons. (a) Contract employer SWAT had workers interacting with the piping and was not informed of the process hazards. (b) Contract employer Turn 2 had workers in the area of the piping and was not informed of the process hazards.
Recent events (3)
- — F (S) $0
- — C (S) $13653
- — Z (S) $13653
1910.119 L01
- Issued
- Aug 26, 2021
- Abate by
- Sep 30, 2021
- Penalty
- Initial $13,653 · Current $13,653
General-duty citation text
29 CFR 1910.119(l)(1):The employer did not implement procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process: On or about February 27, 2021 and at times prior thereto in at the Lion Oil Refinery in El Dorado, AR the employer did not implement procedures to manage changes to process unit. (a) Piping was added to the process in Unit 6 to allow the Stripper Column to be charged with Naphtha from Unit 9. (b) Piping was added to the process in Unit 9 to allow the Unit 6 Stripper Column to be charged with Naphtha from the Unit 9 process. (c) Process piping was routed in the roadway between Unit 6 and Unit 9.
Recent events (3)
- — F (S) $13653
- — C (S) $13653
- — Z (S) $13653
1910.119 L04
- Issued
- Aug 26, 2021
- Abate by
- Mar 15, 2022
- Penalty
- Initial $7,802 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(l)(4): Process safety information was not updated when a process change covered by 29 CFR 1910.119(l) occurred: On or about February 27, 2021 workers in the Lion Oil Refinery in El Dorado, AR, were exposed to hazards that impact safety when a change to a process covered by 29 CFR 1910.119(l) was made without updating process safety information. (a) In Unit 6, piping was added to the bottom of the Separator Column, but the process safety information, including but not limited to Process Flow Diagrams, Piping and Instrumentation Diagrams, and Piping Specifications were not updated. (b) In Unit 9, a change to Naphtha Piping was made to allow for connection directly to the Unit 6 Separator Column but the process safety information, including but not limited to Process Flow Diagrams, Piping and Instrumentation Diagrams, and Piping Specifications were not updated.
Recent events (3)
- — F (S) $0
- — C (S) $7802
- — Z (S) $7802
1910.119 I01
- Issued
- Aug 26, 2021
- Abate by
- Mar 15, 2022
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(i)(1):Pre-startup safety review was not performed when modifications to existing facilities significant enough to require a change in the process safety information were made: (a) On or about February 27, 2021 in Unit 6 and Unit 9 of the Lion Oil Refinery in El Dorado, AR, workers were exposed to hazards associated with chemical release, fire and explosion when a pre-startup safety review of a changes to the process was not conducted prior to placing the modified process in service.
Recent events (3)
- — F (S) $0
- — C (S) $13653
- — Z (S) $13653
1910.106 C03
- Issued
- Aug 26, 2021
- Abate by
- Mar 15, 2022
- Penalty
- Initial $13,653 · Current $13,653
General-duty citation text
29 CFR 1910.106(c)(3): Above ground piping with threaded joints used for transfer of flammable liquid was not secured to prevent disengagement at the fitting and the piping system was not so designed that any spill resulting from such disengagement could not unduly expose persons, important buildings or structures, and could be readily controlled by remote valves: (a) On or about February 27, 2021 in the process area near the Stripper Column in Unit #6 at the Lion Oil Refinery in El Dorado, AR, workers were exposed to fire and explosion hazard when above ground threaded piping used for transferring Naphtha between Units #6 and #9 was not secured to prevent disengagement of threaded joints at the fittings and/or so designed that any spill resulting from such disengagement could not unduly expose persons, important buildings or structures. Additionally, the piping was not readily controlled by remote valves.
Recent events (3)
- — F (S) $13653
- — C (S) $13653
- — Z (S) $13653
1910.106 C04
- Issued
- Aug 26, 2021
- Abate by
- Mar 15, 2022
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.106(c)(4): Piping systems were not substantially supported and protected against physical damage: (a) On or about February 27, 2021 in the process area around the Stripper Column in Unit 6 at the Lion Oil Refinery in El Dorado, AR, workers were exposed to fire and explosion hazard when the piping system installed to transfer Naphtha from Unit 9 to Unit 6 was not substantially supported and protected against physical damage.
Recent events (3)
- — F (S) $0
- — C (S) $13653
- — Z (S) $13653
1910.106 C07
- Issued
- Aug 26, 2021
- Abate by
- Mar 22, 2022
- Penalty
- Initial $9,753 · Current $13,653
General-duty citation text
29 CFR 1910.106(c)(7): Before being covered, enclosed, or placed in use, all piping was not hydrostatically tested to 150 percent of the maximum anticipated pressure of the system, or pneumatically tested to 110 percent of the maximum anticipated pressure of the system, but not less than 5 pounds per square inch gauge at the highest point of the system. Test was not maintained for a sufficient time to complete visual inspection of all joints and connections, but for at least 10 minutes: (a) On or about February 27, 2021 in the process area around the Stripper Column in Unit 6 at the Lion Oil Refinery in El Dorado, AR, workers were exposed to fire and explosion hazard when piping installed to charge the Unit 6 Stripper column with Naphtha from Unit 9 was not hydrostatically tested prior to being placed in use.
Recent events (3)
- — F (O) $13653
- — C (S) $9753
- — Z (S) $9753
More inspections at Delek US
View Delek US's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345169197.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.