ELK GROVE VILLAGE, IL —
OSHA Inspection: AMITRON, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AMITRON, INC. in 2001 LANDMEIER ROAD, ELK GROVE VILLAGE, IL 60007 (NAICS 334418). OSHA activity number 345225809.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMITRON, INC.
- Site address
- 2001 LANDMEIER ROAD
- City
- ELK GROVE VILLAGE
- State
- IL
- ZIP
- 60007
- Mailing
- 2001 LANDMEIER ROAD, ELK GROVE VILLAGE, IL 60007
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 334418
- Employees
- 120
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.22 A03
- Issued
- Apr 30, 2021
- Abate by
- May 26, 2021
- Penalty
- Initial $5,266 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.22(a)(3): The employer did not ensure walking-working surfaces were maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice. a) Plating Department- On March 30, 2021, the employer did not ensure that the floor near the chemical storage area, next to the emergency exit, was maintained free of damage caused by corrosion. b) Plating Department- On March 30, 2021, the employer did not ensure that the floor near the water treatment area, next to the operator's workstation located near the wall, was maintained free of slip hazards from water accumulation caused by leaks. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (S) $3000
- — Z (S) $5266
1910.28 B01 I A
- Issued
- Apr 30, 2021
- Abate by
- May 26, 2021
- Penalty
- Initial $7,022 · Current $4,300 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i)(A):The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level was protected from falling by a standard guardrail system. a) Warehouse- On or about March 29, 2021, the employer did not ensure that the unprotected side of the mezzanine storage space, approximately eight feet above ground level, was guarded with a standard guardrail system when employees accessed the area for material or equipment. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (S) $4300
- — Z (S) $7022
1910.303 B02
- Issued
- Apr 30, 2021
- Abate by
- May 26, 2021
- Penalty
- Initial $5,266 · Current $1,200 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Plating Department/Copper Line- On March 30, 2021, the employer did not ensure that all electrical equipment was installed and used in accordance with instructions included in the listing and labeling. An orange extension cord was connected in series (daisy chained) to another orange extension cord that powered the heater tape. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (O) $1200
- — Z (S) $5266
1910.305 G01 IV A
- Issued
- Apr 30, 2021
- Abate by
- May 26, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Plating Department- On March 30, 2021, a power strips was used as a substitute for fixed wiring to supply power to a bench light over the Plating Workstation. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.334 A02 I
- Issued
- Apr 30, 2021
- Abate by
- May 12, 2021
- Penalty
- Initial $5,266 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): The employer did not ensure that all flexible cords were inspected prior to use in order to identify hazards and ensure that they were free of defects and damage that may expose employees to injury. a) Electroless Department- On March 30, 2021, the outer jacket of the power cord on the portable fan was separated from the motor plate housing, exposing live electrical wires. b) Plating Department- On March 30, 2021, the outlet box on the Plating Line separated from the fixed conduit, exposing live electrical wires. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (S) $3000
- — Z (S) $5266
1910.303 B07 IV
- Issued
- Apr 30, 2021
- Abate by
- May 26, 2021
- Penalty
- Initial $986 · Current $500 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a) Process Department- On March 30, 2021, the employer did not ensure that electrical equipment was free of damage and recognized hazards, such as visible corrosion on the electrical distribution board cover. b) Plating Department- On March 30, 2021, the employer did not ensure that electrical equipment was free of damage and recognized hazards, such as visible corrosion on the electrical disconnect and two electric panel boards. c) Electroless Department- On March 30, 2021, the employer did not ensure that electrical equipment was free of damage and recognized hazards, such as visible corrosion on the faceplate of a 110 Volt junction box. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (O) $500
- — Z (O) $986
1910.303 G01
- Issued
- Apr 30, 2021
- Abate by
- May 26, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Process Department- On March 30, 2021, the employer did not ensure that there was a safe working space around the electrical panels. An electrical distribution board was blocked by stored chemicals in the Process Department. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Amitron, INC.
View Amitron, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 334418)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345225809.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.