Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEFENSE COMMISSARY AGENCY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DEFENSE COMMISSARY AGENCY in 5800 WESTOVER AVE, JBER, AK 99506 (NAICS 445110). OSHA activity number 345262455.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Defense Commissary Agency — free Get an email when a new federal OSHA severe-injury report for Defense Commissary Agency is published. One employer, no account, unsubscribe in one click.
Site address
5800 WESTOVER AVE
City
JBER
State
AK
ZIP
99506
Mailing
5800 WESTOVER AVE, JBER, AK 99506
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445110
Employees
80
Ownership type
D

5 citations on file for this inspection.

1910.23 B10

Serious Gravity 5 3 instances 25 exposed
Issued
Oct 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.23(b)(10): The employer did not ensure that any ladder with structural or other defects as immediately tagged "Dangerous: Do Not Use" or with similar language in accordance with � 1910.145 and removed from service until repaired in accordance with � 1910.22(d), or replaced.  a) Commissary Warehouse:  On or about April 20, 2021, employees used stair ladders with damaged steps and structural cross members to retrieve items stored in the aisle, exposing employees to fall hazards.
Recent events (1)
  • — Z (S) $0

1910.36 G02

Serious Gravity 5 1 instance 25 exposed
Issued
Oct 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.36(g)(2): Exit access(s) were not at least 28 inches (71.1 cm) wide at all points.  a)  Commissary  Warehouse:  On or about April 20, 2021, aisles leading to the exit doors were blocked with pallets of dry goods and equipment exposing employees to delayed egress and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 25 exposed
Issued
Oct 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)  Commissary Warehouse, Eastern dividing wall:  On or about April 20, 2021, Relocatable Power Tap (RPT)  was  connected in series to another RPT, exposing employees to fire and electrical hazard.
Recent events (1)
  • — Z (S) $0

1910.303 G01 I B

Repeat Gravity 5 3 instances 25 exposed
Issued
Oct 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater:  a)  Dry storage warehouse, Door C:  On and or about April 20, 2021, pallet containing materials were place in front of the electrical panel  restricting working space and blocking access to the panel, exposing employees to fire and electrical hazards.  b)  Dry storage warehouse, Door D:  On and or about April 20, 2021, pallet containing materials were place in front of the electrical panel  restricting working space and blocking access to the panel, exposing employees to fire and electrical hazards.  c)  Dry storage warehouse, Door E:  On and or about April 20, 2021, pallet containing materials were place in front of the electrical panel  restricting working space and blocking access to the panel, exposing employees to fire and electrical hazards.  The Defense Commissary Agency was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(1)(i)(B) ), which was contained in OSHA inspection number 1524271, citation number 1,  item number 3 and was affirmed as a final order on May 25, 2021, with respect to a workplace located at 689 North Terminal Road San Juan, Puerto Rico.
Recent events (1)
  • — Z (R) $0

1904.40 A

Other-than-serious 1 instance 25 exposed
Issued
Oct 8, 2021
Abate by
Oct 18, 2021
Penalty
Initial $0 · Current $0
29 CFR  1904.40(a): The employer did not provide an authorized government representative the records within the four business hours.  a)  Commissary:  On or about April 20, 2021, the employer did not provide the OSHA Log(s) upon request at the time of the walkaround within four (4) hours of the request.
Recent events (1)
  • — Z (O) $0

View Defense Commissary Agency's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345262455.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.