OSHA Inspection: GREAT ELECTRIC GROUP, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GREAT ELECTRIC GROUP, LLC in 175 BROAD STREET, GLENS FALLS, NY 12804 (NAICS 238210). OSHA activity number 345363089.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Great Electric Group, LLC — free Get an email when a new federal OSHA severe-injury report for Great Electric Group, LLC is published. One employer, no account, unsubscribe in one click.
Site address
175 BROAD STREET
City
GLENS FALLS
State
NY
ZIP
12804
Mailing
687 EASTLINE RD., BALLSTON SPA, NY 12020
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Oct 4, 2021
Penalty
Initial $4,096 · Current $0 Reduced
29 CFR  OSH ACT of 1970 Section (5)(a)(1):  The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical shock and arc flash hazards:   (a) During installation of a generator transfer switch and related components in the mechanical room at Hannaford Supermarket in Glens Falls, NY:  On or prior to 6/14/21, employees performed work on energized equipment, including, but not limited to a 1200 Amp 3 phase Main Distribution Panel operating at 480 volts, without performing an arc-flash hazard analysis, using insulated tools, or determining if deenergized work was infeasible or created an increased risk.
Recent events (3)
  • — F (S) $0
  • — C (S) $4096
  • — Z (S) $4096

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 4, 2021
Penalty
Initial $4,096 · Current $3,550 Reduced
29 CFR  1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  (a) During installation of a generator transfer switch and related components in the mechanical room at Hannaford Supermarket in Glens Falls, NY:  On or prior to 6/14/21, employees performed work on energized equipment, including, but not limited to a 1200 Amp 3 phase Main Distribution Panel operating at 480 volts, without protection from electric shock.
Recent events (3)
  • — F (S) $3550
  • — C (S) $4096
  • — Z (S) $4096

1926.95 A

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 4, 2021
Penalty
Initial $27,306 · Current $3,550 Reduced
29 CFR  1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided:  (a) During installation of a generator transfer switch and related components in the mechanical room at Hannaford Supermarket in Glens Falls, NY:  On or prior to 6/13/21, employees were not provided with arc flash protective gear while performing work within the Flash Protection Boundary of a 1200 Amp, 3 phase Main Distribution Panel (MDP 1A) operating at 480 volts, with a Flash Hazard Category of 2.
Recent events (3)
  • — F (S) $3550
  • — C (W) $27306
  • — Z (W) $27306

View Great Electric Group, LLC's full OSHA safety record →