SAIPAN, MP —
OSHA Inspection: COCA-COLA BEVERAGE CO. MICRONESIA INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of COCA-COLA BEVERAGE CO. MICRONESIA INC. in LOT 1774-1 CHALAN PALE ARNOLD DR. CHALAN LAU LAU, SAIPAN, MP 96950 (NAICS 493110). OSHA activity number 345388722.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COCA-COLA BEVERAGE CO. MICRONESIA INC.
- Site address
- LOT 1774-1 CHALAN PALE ARNOLD DR. CHALAN LAU LAU
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- P.O. BOX 500266, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 26
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 29, 2021
- Penalty
- Initial $4,096 · Current $2,867 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or�labeled electrical�equipment was�not used�or installed�in accordance�with instructions�included in�the listing�or labeling: a. In front of the main office: An electrical receptacle box designed to be installed inside of a wall was used on the end of an extension cord. Employees were exposed to fire and electrical hazards b. Salvage area: An electrical receptacle box designed to be installed inside of a wall was used on the end of an extension cord. Employees were exposed to fire and electrical hazards c. Salvage area floor: An electrical receptacle box designed to be installed inside of a wall was used on the end of an extension cord. Employees were exposed to fire and electrical hazards
Recent events (2)
- — I (S) $2867.2
- — Z (S) $4096
1910.305 B01 I
- Issued
- Sep 29, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed: Cords were not protected from abrasion and opening through which conductors entered were not effectively closed. a. In front of the main office: Extension cord connected to a panel and a receptacle box was not protected from abrasion and openings on the panel and the receptacle box were not effectively closed, exposing employees to shock hazards. b. Salvage area: Extension cord connected to a panel and a receptacle box was not protected from abrasion and openings on the panel and the receptacle box were not effectively closed, exposing employees to shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Sep 29, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Electrical cords were connected directly to the panel boxes exposing employees to shock hazards. a. In front of the main office: a cord with a junction box on one end was connected directly to the panel box's internal mechanism exposing employees to shock hazards. b. Salvage area: a cord with a junction box on one end was connected directly to the panel box exposing employees to shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 II
- Issued
- Sep 29, 2021
- Penalty
- Initial $4,096 · Current $2,867 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap: Salvage area north wall: Wires were spliced to a flexible cord used to power a light used light an area outside the facility. Employees were exposed to fire and electrical hazards.
Recent events (2)
- — I (S) $2867.2
- — Z (S) $4096
1910.157 E02
- Issued
- Sep 29, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): At this establishment, the employer was not visually inspecting the portable fire extinguishers at least monthly. Throughout the warehouse: Monthly inspections to ensure fire extinguishers were serviceable and operational for incipient firefighting were not conducted, exposing employees to fire hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 A02 X
- Issued
- Sep 29, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: Salvage area: The extension cord used to power a fan was routed under boxes and various crates, exposing employees to fire and electrical hazards
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.101 B
- Issued
- Sep 29, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: Southwest corner of warehouse: Compressed gas cylinders, that were not in use, were not secured to prevent from falling over exposing employees to struck-by hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Coca-Cola Beverage CO. Micronesia INC.
View Coca-Cola Beverage CO. Micronesia INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in MP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345388722.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.