Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FERRIE FRANZMANN INDUSTRIES, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of FERRIE FRANZMANN INDUSTRIES, LLC in 1020 SARGENT RD, DALLAS, TX 75235 (NAICS 221122). OSHA activity number 345399315.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ferrie Franzmann Industries, LLC — free Get an email when a new federal OSHA severe-injury report for Ferrie Franzmann Industries, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1020 SARGENT RD
City
DALLAS
State
TX
ZIP
75235
Mailing
1505 W 3RD AVE, DENVER, CO 80223
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
2
Ownership type
A

9 citations on file for this inspection.

1910.269 A02 II E

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR 1910.269(a)(2)(ii)(E):Each qualified employee was not trained and competent in the recognition of electrical hazards to which the employee may be exposed and the skills and techniques necessary to control or avoid these hazards:  (a) On or about June 29, 2021, two employees installing electrical equipment in substation 1 were exposed to an electrical hazard when the employer did not train the employees as qualified employees and they lacked the competence, skill, and techniques necessary to control or avoid the hazard.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

1910.269 A03 III

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $0 Reduced
29 CFR 1910.269(a)(3)(iii):The contract employer and the host employer did not coordinate their work rules and procedures so that each employee of the contract employer and the host employer was protected as required by this section:  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when the employer did not coordinate their work rules and procedures with the host employer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $12288

1910.269 L01 III

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR 1910.269(l)(1)(iii): Electric lines and equipment were not considered and treated as energized unless they had been de-energized in accordance with paragraph (d) or (m) of this section:  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when the equipment was not treated as energized.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

1910.269 M02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR  1910.269(m)(2)(i):The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance did not make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (m)(3) of this section) and is responsible for the clearance.  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when the requirements of paragraph (m)(3) of this section were not met.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

1910.269 M03 II

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $0 Reduced
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized/open, rendered inoperable if possible, and then did not ensure that such means were tagged to indicate that employees were at work:  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when the known sources of electric energy that might be supplied to the equipment were not de-energized/open, rendered inoperable if possible, and tagged to indicate employees were at work.
Recent events (2)
  • — I (S) $0
  • — Z (S) $12288

1910.269 U04 III

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR  1910.269(u)(4)(iii): The employer did not ensure that unqualified persons may not enter the rooms or other spaces while the electric supply lines or equipment were energized:  (a) On or about June 29, 2021, two unqualified employees installing electrical equipment were exposed to an electrical hazard when they were allowed to enter substation 1 while the electrical equipment was energized.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

1910.333 C02

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR  1910.333(c)(2):The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools:  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when the circuits they were working on were energized and they were not familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

1910.334 C03

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR 1910.334(c)(3): The employer did not ensure that test instruments and equipment and their accessories were rated for the circuits and equipment to which they will be connected and designed for the environment in which they will be used:  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when the test instrument they used was not rated for the circuit it was connected to.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 26, 2021
Abate by
Nov 22, 2021
Penalty
Initial $12,288 · Current $7,373 Reduced
29 CFR 1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  (a) On or about June 29, 2021, two employees installing electrical equipment were exposed to an electrical hazard when they were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.
Recent events (2)
  • — I (S) $7372.8
  • — Z (S) $12288

View Ferrie Franzmann Industries, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345399315.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.