ROCKLAND, WI —
OSHA Inspection: KONKEL CUSTOM WOODWORKS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of KONKEL CUSTOM WOODWORKS, INC. in 504 E. ROCK STREET, ROCKLAND, WI 54653 (NAICS 321912). OSHA activity number 345504989.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KONKEL CUSTOM WOODWORKS, INC.
- Site address
- 504 E. ROCK STREET
- City
- ROCKLAND
- State
- WI
- ZIP
- 54653
- Mailing
- 504 E. ROCK STREET, ROCKLAND, WI 54653
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321912
- Employees
- 25
- Ownership type
- A
Citations
18 citations on file for this inspection.
1910.22 A01
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $0 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. On or about August 30, 2021, the employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces in areas including, but not limited to, the Room under the Silo were kept in a clean, orderly, and sanitary condition in that there was an accumulation of combustible dust. In the alternative, 29 CFR 1910.176(c): Storage areas were not kept free from accumulation of materials that constituted hazards from tripping, fire, explosion or pest harborage: On or about August 30, 2021, the employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces in areas including, but not limited to, the Room under the Silo were kept in a clean, orderly, and sanitary condition in that there was an accumulation of combustible dust.
Recent events (3)
- — F (S) $0
- — C (S) $4144
- — Z (S) $4144
1910.28 B03 IV
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $2,072 Reduced
General-duty citation text
29 CFR 1910.28(b)(3)(iv):29 CFR 1910.28(b)(3)(iv): The employer did not provide that each employee be protected from falling into a ladderway floor hole or ladderway platform hole by a guardrail system and toeboards erected on all exposed sides, except at the entrance to the hole, where a self-closing gate or an offset must be used. On or about August 30, 2021, the employer did not provide that each employee, including the maintenance technician accessing the Silo Platform, be protected from falling into a ladderway platform hole by a guardrail system and toeboards erected on all exposed sides, except at the entrance to the hole, where a self-closing gate or an offset must be used.
Recent events (3)
- — F (S) $2072
- — C (S) $4144
- — Z (S) $4144
1910.28 B11 II
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,972 · Current $2,486 Reduced
General-duty citation text
29 CFR 1910.28(b)(11)(ii): The employer did not ensure that each flight of stairs having at least 3 treads and at least 4 risers is equipped with stair rail systems and handrails as described in 29 CFR 1910.28 Table D-2-Stairway Handrail Requirements. On or about August 30, 2021, the employer did not ensure that each flight of stairs having at least 3 treads and at least 4 risers used by employees to access the Grading Table in the Stickering Area was equipped with stair rail systems and handrails as described in 29 CFR 1910.28 Table D-2-Stairway Handrail Requirements.
Recent events (3)
- — F (S) $2486
- — C (S) $4972
- — Z (S) $4972
1910.147 C01
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $4,144
General-duty citation text
29 CFR 1910.147(c)(1):The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: On or about August 30, 2021, the employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative.
Recent events (3)
- — F (S) $4144
- — C (S) $4144
- — Z (S) $4144
1910.147 C04 I
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i):Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: On or about August 30, 2021, the employer did not ensure that procedures were developed, documented and utilized for the control of potentially hazardous energy, such as, but not limited, to mechanical energy, for employees who were performing serving operations on equipment such as, but not limited to, chain(s) in the Boiler Room and chain(s) in Room under the Silo.
Recent events (3)
- — F (S) $0
- — C (S) $4144
- — Z (S) $4144
1910.147 C07 I
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i):The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices: On or about August 30, 2021, the employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices while clearing jams from the Newman S-282 Planer Machine (S/N 14606) or lubricating chains in the Boiler Room Pit and Room under the Silo.
Recent events (3)
- — F (S) $0
- — C (S) $4144
- — Z (S) $4144
1910.178 L01 I
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,972 · Current $2,486 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i):The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): On or about August 30, 2021, the employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation.
Recent events (3)
- — F (S) $2486
- — C (S) $4972
- — Z (S) $4972
1910.212 A01
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $5,801 · Current $5,801
General-duty citation text
29 CFR 1910.212(a)(1):One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about August 30, 2021, one or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks while operating the Newman S-282 Planer Machine (S/N 14606) in Plant 1.
Recent events (3)
- — F (S) $5801
- — C (S) $5801
- — Z (S) $5801
1910.305 B01 I
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $3,315 · Current $3,315
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a) On or about August 30, 2021, the conductors supplying electrical power to the Newman planer (Model S-282) in Plant 1 were not protected from abrasion due to the flexible conduit being pulled away from the motor junction box. b) On or about August 30, 2021, the conductors for the lumber conveyor in Plant 1 were not protected from physical damage due to the floor mounted conduit being pulled away from the floor-mounted cutout box.
Recent events (3)
- — F (S) $3315
- — C (S) $3315
- — Z (S) $3315
1910.305 G01 IV A
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $3,315 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about August 30, 2021, the flexible cord providing electrical power to the Upcut Saw in Plant 1 was used as a substitute for fixed wiring.
Recent events (3)
- — F (S) $0
- — C (S) $3315
- — Z (S) $3315
1910.305 G02 III
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii):Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about August 30, 2021, the flexible cord for the Upcut Saw in Plant 1 was not connected to the male electrical plug body so that strain relief was provided to prevent the pulling of the cord from being transmitted to the terminal screws in the plug body.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.307 C
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $4,144
General-duty citation text
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: On or about August 30, 2021, employees working beneath the wood silo were exposed to hazards from non-intrinsically safety equipment, wiring method and installations for equipment, such as fluorescent lights, ballasts and uncovered electrical outlets, in a hazardous (classified) location.
Recent events (3)
- — F (S) $4144
- — C (S) $4144
- — Z (S) $4144
1910.335 A01 I
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $5,801 · Current $2,901 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about August 30, 2021, employee(s) were not provided with electrical protective equipment suitable for protection of the hands and body.
Recent events (3)
- — F (S) $2900.5
- — C (S) $5801
- — Z (S) $5801
1910.1200 H01
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $4,144 · Current $2,072 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: On or about August 30, 2021, an Maintenance Technician working in the Room Under Silo cleaning wood dust from the room was not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area.
Recent events (3)
- — F (S) $2072
- — C (S) $4144
- — Z (S) $4144
1904.40 A
- Issued
- Feb 9, 2022
- Abate by
- Feb 24, 2022
- Penalty
- Initial $829 · Current $415 Reduced
General-duty citation text
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours. On or about August 30, 2021, the employer failed to provide copies of the injury and illness records to an authorized representative. An employer may use the business hours of the establishment at which the records are located when calculating the deadline
Recent events (3)
- — F (O) $414.5
- — C (O) $829
- — Z (O) $829
1910.303 B02
- Issued
- Feb 9, 2022
- Abate by
- Feb 24, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about August 30, 2021, equipment in the Plant 1 Break Area was plugged into a relocatable power strip that was not used or installed in accordance with instructions included in the listing or labeling.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.303 G01 I B
- Issued
- Feb 9, 2022
- Abate by
- Mar 3, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater: On or about August 30, 2021, electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater:
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.305 G01 IV D
- Issued
- Feb 9, 2022
- Abate by
- Feb 24, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D):Flexible cords were attached to building surfaces: On or about August 30, 2021, flexible cord(s) in the Boiler Room were attached to building surfaces.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Konkel Custom Woodworks, INC.
View Konkel Custom Woodworks, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 321912)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345504989.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.