On , OSHA opened a referral safety inspection of UNION ELECTRIC STEEL CORPORATION in 31 UNION ELECTRIC ROAD, BURGETTSTOWN, PA 15021 (NAICS 331210). OSHA activity number 345573174.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Union Electric Steel Corporation — free Get an email when a new federal OSHA severe-injury report for Union Electric Steel Corporation is published. One employer, no account, unsubscribe in one click.
Site address
31 UNION ELECTRIC ROAD
City
BURGETTSTOWN
State
PA
ZIP
15021
Mailing
31 UNION ELECTRIC ROAD, BURGETTSTOWN, PA 15021
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331210
Employees
175
Ownership type
A

3 citations on file for this inspection.

1910.333 A02

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2021
Abate by
Jan 20, 2022
Penalty
Initial $9,753 · Current $6,000 Reduced
29 CFR  1910.333(a)(2):  Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:   a) Jobsite, 31 Union Electric Road, Burgettstown, PA 15021:  On or about September 22, 2021, employees were exposed to electrical shock hazards when exposed to energized conductors (480 volt, 3 phase) located inside of the control panels of the lathes including the #24 tailstock lathe.   Safety-related work practices were not developed or used to protect employees from electrical shock hazards while preforming various types of troubleshooting activities on the lathes including, but not limited to, checking the quill, checking amperages and checking inputs/outputs to different relays.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $9753

1910.335 A01 I

Other-than-serious Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2021
Abate by
Jan 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:   a) Jobsite, 31 Union Electric Road, Burgettstown, PA 15021:  On or about September 22, 2021, employees engaged in troubleshooting the lathes, including lathe #24, where not using proper personal protective equipment during troubleshooting activities.  Employees use Tilsatec brand TTP203 leather gloves while working inside of the lathe control panels which contain energized conductors (480 Volts).  The gloves do not offer an adequate level of protection to the employee's hands and arms when they are required to troubleshoot components inside of the lathe control boxes.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.335 A01 V

Other-than-serious Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2021
Abate by
Jan 20, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.335(a)(1)(v): Employees did not wear protective equipment for the eyes or face wherever there was danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion:   a) Jobsite, 31 Union Electric Road, Burgettstown, PA 15021:  On or about September 22, 2021, employees engaged in troubleshooting the lathes, including lathe #24, where not protected from electric arc flash or burns to the eyes and face while engaged in troubleshooting activities.