APPLETON, WI —
OSHA Inspection: MCCLINTOCK CABINETS INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MCCLINTOCK CABINETS INC. in N3151 STATE ROAD 47, APPLETON, WI 54913 (NAICS 337110). OSHA activity number 345595235.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MCCLINTOCK CABINETS INC.
- Site address
- N3151 STATE ROAD 47
- City
- APPLETON
- State
- WI
- ZIP
- 54913
- Mailing
- N3151 STATE ROAD 47, APPLETON, WI 54913
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337110
- Employees
- 6
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.304 G05
- Issued
- Apr 1, 2022
- Abate by
- Apr 29, 2022
- Penalty
- Initial $3,108 · Current $1,554 Reduced
General-duty citation text
29 CFR 1910.304(g)(5):Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. a. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI 54913, the plug on the Sears Craftsman 12-inch electric band saw was missing the ground pin which exposed employees to potential electric hazard. b. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI 54913, the plug on the Ventimatic BF24TF YEL MaxxAir 24-inch floor fan was missing the ground pin which exposed employees to potential electric hazard. c. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI 54913, the plug on the Patton Electric Industrial Floor Fan was missing the ground pin which exposed employees to potential electric hazard.
Recent events (2)
- — I (S) $1554
- — Z (S) $3108
1910.305 B01 II
- Issued
- Apr 1, 2022
- Abate by
- Apr 29, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii):Unused openings in cabinets, boxes, and fittings shall be effectively closed. a. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI 54913, an electric junction box was not effectively closed. The junction box, located on the edge bander at the southwestern corner of the production area, was missing a knockout. b. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI 54913, an electric junction box was not effectively closed. The junction box, on the western wall of the production area, had an opening on the top where a piece of conduit was removed. c. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI 54913, an electric cabinet was not effectively closed. The electric cabinet in the (old break room) had an opening in the breaker area and was missing two breakers along with a missing cover on the bottom of the cabinet.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A02 II
- Issued
- Apr 1, 2022
- Abate by
- Apr 29, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii):If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made. a) On or about October 20, 2021, employees were exposed to potential shock hazards when working with the Sears Craftsman 12-inch electric band saw. The power cord had exposed wires at the base of the plug and employees were exposed to electric shock when plugging in or unplugging the power cord. b) On or about October 20, 2021, employees were exposed to potential shock hazards when working with a Southworth 2000-pound capacity lift table. The power cable had exposed wires at the base of the plug and employees were exposed to electric shock when plugging in or unplugging the power cord.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I A
- Issued
- Apr 1, 2022
- Abate by
- Jul 31, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed; On or about October 20, 2021, the depth of the working space between the electrical panel, which is used as the dust collector disconnect, and the dust collector in the southeastern corner of the production area was less than three feet as indicated in Table S-1.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B02 I
- Issued
- Apr 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i):All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI, employees were exposed to electrical hazards from a junction box missing a cover.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV D
- Issued
- Apr 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D):Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where attached to building surfaces; On or about October 20, 2021, at the establishment located at N3151 State Road 47 Appleton, WI, a flexible cord was attached to the building surface spanning a passageway between the northeastern and southeastern sides of the production area.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Mcclintock Cabinets INC.
View Mcclintock Cabinets INC.'s full OSHA safety record →
More inspections in this industry (NAICS 337110)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345595235.