Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: JOUNIEHXPRESS LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of JOUNIEHXPRESS LLC in 2001 POLYTECHNIC LN, MARIETTA, GA 30060 (NAICS 811198). OSHA activity number 345610513.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jouniehxpress LLC — free Get an email when a new federal OSHA severe-injury report for Jouniehxpress LLC is published. One employer, no account, unsubscribe in one click.
Establishment
JOUNIEHXPRESS LLC
Site address
2001 POLYTECHNIC LN
City
MARIETTA
State
GA
ZIP
30060
Mailing
2001 POLYTECHNIC LN, MARIETTA, GA 30060
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811198
Employees
15
Ownership type
A

7 citations on file for this inspection.

1910.147 C01

Serious Gravity 5 2 instances 1 exposed
Issued
Apr 27, 2022
Abate by
May 23, 2022
Penalty
Initial $3,315 · Current $1,989 Reduced
29 CFR  1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  a) Production Area: On or about October 29, 2021, and at times prior, the employer exposed an employee to struck-by hazards, in that the employer did not develop and implement a control of hazardous energy program where an employee performs servicing and maintenance on the  "LS Industries" RBX-L Alloy Rim Blaster.  b) Production Area: On or about October 29, 2021, and at times prior, the employer exposed an employee to struck-by hazards, in that the employer did not develop and implement a control of hazardous energy program where an employee performs servicing and maintenance on the  "Lehigh Machinery" model MR-2540 lathe (serial number T0115010213).
Recent events (2)
  • — I (S) $1989
  • — Z (S) $3315

1910.305 B02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 27, 2022
Abate by
May 23, 2022
Penalty
Initial $2,486 · Current $1,492 Reduced
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   a) Strip Tank Area: On or about October 29, 2021, the employer exposed employees to electrical hazards, in that a wall-mounted metal outlet box containing a 110-volt electrical receptacle did not have a faceplate to protect employees who connect and disconnect the cord and plug of an in-wall fan to the receptacle to turn the fan on and off.
Recent events (2)
  • — I (S) $1491.6
  • — Z (S) $2486

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 27, 2022
Abate by
May 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a) Strip Tank Area: On or about October 29, 2021, the employer exposed employees to electrical shock and fire hazards while utilizing an in-wall exhaust fan that was connected to an extension cord and tied to the building structure.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 H03

Other-than-serious 1 instance 4 exposed
Issued
Apr 27, 2022
Abate by
May 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.36(h)(3):  Outdoor exit route(s) were not reasonably straight and did not have smooth, solid, substantially level walkways:  a) Exterior West Wall of Production Area: On or about October 29, 2021, and at times prior, the employer exposed employees to trip and fall hazards, in that the wooden landing at the bottom of the exterior stairs descending from the exit discharge was not maintained in a smooth, solid and level condition where the landing was not fully planked and the remaining wood was significantly deteriorated and broken.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.101 B

Other-than-serious 1 instance 4 exposed
Issued
Apr 27, 2022
Abate by
May 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tank cars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:   a) Production Area: On or about October 29, 2021, and at times prior, the employer exposed employees to struck-by hazards, in that the employer did not ensure that an Argon cylinder located next to the welding machine was secured to prevent tipping.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 C04

Other-than-serious 1 instance 15 exposed
Issued
Apr 27, 2022
Abate by
May 23, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(4):Portable fire extinguishers were not maintained in a fully charged and operable condition:  a) Paint Booth Area: On or about October 29, 2021, and at times prior, the employer exposed employees to fire hazards, in that an "Amerex"  model 456, dry chemical fire extinguisher was not maintained in a fully charged condition.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E02

Other-than-serious 1 instance 15 exposed
Issued
Apr 27, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:   a) Paint Booth Area: On or about October 29, 2021, and at times prior, the employer exposed employees to fire hazards, in that an "Amerex"  model 456, dry chemical fire extinguisher was not visually inspected at least monthly.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Jouniehxpress LLC's full OSHA safety record →