GALION, OH —
OSHA Inspection: COVERT MANUFACTURING INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of COVERT MANUFACTURING INC. in 328 SOUTH EAST ST., GALION, OH 44833 (NAICS 333514). OSHA activity number 345618987.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COVERT MANUFACTURING INC.
- Site address
- 328 SOUTH EAST ST.
- City
- GALION
- State
- OH
- ZIP
- 44833
- Mailing
- 328 SOUTH EAST ST., GALION, OH 44833
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333514
- Employees
- 200
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01
- Issued
- Nov 30, 2021
- Abate by
- Dec 9, 2021
- Penalty
- Initial $7,461 · Current $7,461
General-duty citation text
29 CFR 1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about November 4, 2021, the employer did not ensure sufficient access and working space was provided to electrical boxes in the machine shop - vertical department, limiting the ability to shut off of power in the event of an emergency.
Recent events (1)
- — Z (S) $7461
1910.305 B01 I
- Issued
- Nov 30, 2021
- Abate by
- Dec 9, 2021
- Penalty
- Initial $7,461 · Current $7,461
General-duty citation text
29 CFR 1910.305(b)(1)(i):Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: On or about November 4, 2021 the employer in the coolant storage/pump room, did not ensure that all flexible cords were properly secured and protected from the possibility of abrasions/fraying, exposing employees to electrical shock.
Recent events (1)
- — Z (S) $7461
1910.305 G01 IV A
- Issued
- Nov 30, 2021
- Abate by
- Dec 9, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about November 4, 2021 the employer in the coolant storage room, used flexible cords in place of fixed/permanent 480 volt wiring to power the coolant sump pump out machine exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
More inspections at Covert Manufacturing INC.
View Covert Manufacturing INC.'s full OSHA safety record →
More inspections in this industry (NAICS 333514)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345618987.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.