Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BLUEWATER RESORT & CASINO

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of BLUEWATER RESORT & CASINO in 11222 RESORT DRIVE ATTN: ERIC MACDONALD, PARKER, AZ 85344 (NAICS 721120). OSHA activity number 345652440.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bluewater Resort & Casino — free Get an email when a new federal OSHA severe-injury report for Bluewater Resort & Casino is published. One employer, no account, unsubscribe in one click.
Site address
11222 RESORT DRIVE ATTN: ERIC MACDONALD
City
PARKER
State
AZ
ZIP
85344
Mailing
11222 RESORT DRIVE, PARKER, AZ 85344
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
260
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 2 instances 2 exposed
Issued
Feb 2, 2022
Penalty
Initial $6,837 · Current $6,837
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   (a)	POOL ROOM: A 3-way splitter was used to provide power to a CAT controller, a white 120V Pre-Wired-back up Electrical Junction Box (Model HCSJBOX) connected to an Aquasol Controller (120V 1.7A), and a pump motor, exposing workers to electrocution and fire hazards.  (b)	POOL ROOM: Three 3-way splitters were used to provide power to three CAT controllers, and three white 120V Pre-Wired-back up Electrical Junction Box (Model HCSJBOX) each connected to an Aquasol Controller (120V 1.7A), exposing workers to electrocution and fire hazards.  (c)	MAIN KITCHEN SERVER STATION: A 15A relocatable power tap was connected to a Cornelius beverage machine, exposing workers to electrocution and fire hazards. (d)	ATRIUM BAR: a power strip was use to provide power for a blender and coffee pot, exposing workers to electrocution and fire hazard.
Recent events (1)
  • — Z (S) $6837

1910.305 G01 IV A

Serious Gravity 1 2 instances 2 exposed
Issued
Feb 2, 2022
Abate by
Feb 9, 2022
Penalty
Initial $6,837 · Current $6,837
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  (a)	3RD FLOOR LAUNDRY ROOM- A black extension cord (12G SJOOW 300V) was used to power the EcoLab chemical feed pump for the commercial washer and dryer, exposing workers to electrocution and fire hazards.   (b)	MAIN KITCHEN SERVER STATION: A Blue extension cord (16G SJTW 200V) was used to power a Bunn Tea pot (14.4A 120V SN TU00325505), exposing workers to electrocution and fire hazards.
Recent events (1)
  • — Z (S) $6837

1910.1030 C01 IV

Other-than-serious 1 instance 30 exposed
Issued
Feb 2, 2022
Abate by
Feb 9, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.1030(c)(1)(iv):The Exposure Control Plan was not reviewed and updated at least annually:  (a) HOTEL: Employee in the housekeeping department have anticipated exposures to blood or other potentially infectious materials (OPIM), and the Exposure Control Plan was not reviewed annually.  The Exposure Control Plan did not include documentation of the last review date.
Recent events (1)
  • — Z (O) $0

View Bluewater Resort & Casino's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345652440.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.