NOGALES, AZ —
OSHA Inspection: US BORDER PATROL - TUCSON SECTOR
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of US BORDER PATROL - TUCSON SECTOR in I-19 CHECKPOINT 1500 N LA QUINTA ROAD, NOGALES, AZ 85621 (NAICS 928110). OSHA activity number 345661953.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- US BORDER PATROL - TUCSON SECTOR
- Site address
- I-19 CHECKPOINT 1500 N LA QUINTA ROAD
- City
- NOGALES
- State
- AZ
- ZIP
- 85621
- Mailing
- 2430 S. SWAN RD., TUCSON, AZ 85711
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 75
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.305 G01 I
- Issued
- Jan 26, 2022
- Abate by
- Feb 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(i):Flexible cords and cables were not approved for conditions of use and location: SECONDARY SEARCH AREA: A 15A relocatable power tap with an (SJT) cord not rated for outdoor use was plugged into an extension cord outside on the ground behind the tent, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 G01 III
- Issued
- Jan 26, 2022
- Abate by
- Feb 2, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iii):Flexible cords used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of 29 CFR 1910.305 were not equipped with an attachment plug and energized from an approved receptacle outlet: SECONDARY SEARCH AREA: Portable forced air diesel heaters were powered by extension cords that were not plugged into an acceptable receptacle, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jan 26, 2022
- Abate by
- Feb 7, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) SECONDARY INSPECTION: Extension cords were used to provide power to fixed locations, exposing employees to electrical shock and fire hazards. b) SEARCH SHED: Extension cords were used to provide power to the shed, exposing employees to electrical shock and fire hazards.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Jan 26, 2022
- Abate by
- Feb 7, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: a) SEARCH AREA SHED - The red extension cord (10G/20A SJTW) use to provide power to the shed, was run through a hole in the exterior wall, exposing employees to fire hazards. b) SEARCH AREA SHED - The yellow extension cord (12G/15A SJTW) use to provide power in the shed, was run through a hole in the exterior wall, exposing employees to fire and electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Jan 26, 2022
- Abate by
- Feb 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii):Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: SEARCH SHED: A red extension cord (10G/20A SJTW, single receptacle, 50ft), was not provided with strain relief, and the outer jacket had separated from the plug at the female end, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 J02 I
- Issued
- Jan 26, 2022
- Abate by
- Feb 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(i):Receptacles were not installed so that an energized attachment plug was not its source of supply: a) SEARCH AREA SHED: A 4-outlet receptacle box mounted to the east wall was powered by a flexible cord with plug attachment, exposing employees to shock hazards.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Jan 26, 2022
- Abate by
- Feb 7, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) SECONDARY SEARCH AREA: A 15A relocatable power tap supplied power to a coffee pot (8.125A), a hot/cold water dispenser (4.5A), Lasko heater (12.5A), a string of lights (0.15A) and two 15A yellow extension cords, exposing employees to electrical shock hazards and burns. b) SECONDARY SEARCH AREA: A 15A relocatable power tap was "daisy chained", exposing employees to electrical shock hazards. The relocatable power tap was plugged into an extension cord (yellow cord #3) and supplied power to three additional extension cords (yellow cords #6 and #7, and white extension cord #1). c) 1-19 CHECKPOINT: Six yellow extension cords (12G/15A SJTW) and a red extension cord (10G/20A SJTW) were "daisy chained" together and in use, exposing employees to electrical shock hazards. The yellow cord #1 was plugged into a 20A wall receptacle and powering a second yellow extension cord, which was powering a third yellow extension cord with 3 receptacle's. This cord (yellow #3) branched out to power the fourth and fifth yellow cords. The fourth yellow extension cord was providing power yellow cord #8 and a portable heater. Yellow cord #8 was providing power to a second portable heater. Yellow cord #5 was providing power to a red extension cord which provide power to a wall mounted receptacle box. The U.S. Border Patrol-Nogales was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 303(b)(2), which was contained in OSHA inspection number 1335083, notice 1, item number 4, issued on September 28, 2018, which was affirmed as a final order on October 25, 2018 with respect to a workplace located at 1500 West La Quinta, Nogales, AZ 85621. The U.S. Border Patrol-Tucson Sector was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 303(b)(2), which was contained in OSHA inspection number 1335138, notice 1, item number 6, issued on September 28, 2018, which was affirmed as a final order on October 24, 2018 with respect to a workplace located at 2430 South Swan Road, Tucson, AZ 85711.
Recent events (1)
- — Z (R) $0
More inspections at US Border Patrol - Tucson Sector
View US Border Patrol - Tucson Sector's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345661953.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.