RUMFORD, RI —
OSHA Inspection: PCL FIXTURES, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of PCL FIXTURES, INC. in 275 FERRIS AVE., RUMFORD, RI 02916 (NAICS 337215). OSHA activity number 345688451.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PCL FIXTURES, INC.
- Site address
- 275 FERRIS AVE.
- City
- RUMFORD
- State
- RI
- ZIP
- 02916
- Mailing
- 275 FERRIS AVENUE, RUMFORD, RI 02916
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337215
- Employees
- 62
- Ownership type
- A
Citations
13 citations on file for this inspection.
1910.22 A01
- Issued
- Jun 9, 2022
- Abate by
- Jul 27, 2022
- Penalty
- Initial $9,136 · Current $5,500 Reduced
E200
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment were kept clean: a) Saw Room and Assembly Area: Employees were working in the area where MDX is processed, which had combustible wood dust buildup located on the pipes, on top of equipment, on overhead structures, and other horizontal surfaces on or about December 10, 2021.
Recent events (2)
- — I (S) $5500
- — Z (S) $9136
1910.22 A02
- Issued
- Jun 9, 2022
- Abate by
- Jul 27, 2022
- Penalty
- Initial $0 · Current $0
E200
General-duty citation text
29 CFR 1910.22(a)(2): : The employer did not ensure that the floor of each workroom is maintained in a clean condition: a) Saw Room and Assembly Area: Employees were exposed to explosive combustible wood dust which was on the floor of the area where MDX and plywood processing was being performed on or about December 10, 2021.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.28 B01 I
- Issued
- Jun 9, 2022
- Abate by
- Jul 13, 2022
- Penalty
- Initial $9,136 · Current $5,500 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i): (a) Covered railroad access area: On or about December 15, 2021, the employer did not ensure that employees walking (in the event of an emergency evacuation) or working (area used to store product) on the deck above the railroad tracks were protected from falling approximately 4.5 feet onto the lower level.
Recent events (2)
- — I (S) $5500
- — Z (S) $9136
1910.37 A02
- Issued
- Jun 9, 2022
- Abate by
- Oct 31, 2022
- Penalty
- Initial $9,136 · Current $5,500 Reduced
General-duty citation text
29 CFR 1910.37(a)(2): Exit routes were not arranged so that employees did not have to travel toward a high hazard area: (a) Saw Room: On or about May 16, 2022, exit routes on the eastern side of the saw room were routed within 20 feet of dust collection bags containing combustible dusts.
Recent events (2)
- — I (S) $5500
- — Z (S) $9136
1910.36 E01
- Issued
- Jun 9, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(e)(1): A side-hinged door was not used to connect rooms to an exit route: (a) Covered railroad access area: On or about December 15, 2021, the employer did not ensure that a doorway, on the exit route located where the covered railroad access area enters into the shipping area, was provided with a side hinged door. It had an overhead roll-up door.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B01
- Issued
- Jun 9, 2022
- Abate by
- Jul 27, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that employees with normal vision could see along the exit route: (a) Covered railroad access area: On or about May 16, 2022, the employer did not ensure that the evacuation route toward the northeast end of this area was provided with adequate lighting.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B02
- Issued
- Jun 9, 2022
- Abate by
- Jul 6, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": (a) Covered railroad access area: On or about December 15, 2021, the employer did not ensure that the evacuation route in this area was clearly visible and marked as an "EXIT". (b) Covered railroad access area: On or about May 16, 2022, the employer did not ensure that the exit door in the northeast side of the area was clearly visible and marked as an "EXIT".
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 III
- Issued
- Jun 9, 2022
- Abate by
- Jul 27, 2022
- Penalty
- Initial $9,136 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iii): Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph: (a) Outside, East Side of Building at the Dust Collection System: On or about December 10, 2021, a flexible cord and plug extension cord was being used in lieu of permanent wiring for wiring of the condensation drain line heater from the dust collection system's bag house operations. (b) Throughout the Establishment: On or about December 10, 2021, flexible cord and plug extension cords were being used in lieu of permanent wiring for the wiring of equipment such as, but not limited to, floor fans and other equipment throughout the facility.
Recent events (2)
- — I (O) $1000
- — Z (S) $9136
1910.307 B
- Issued
- Jun 9, 2022
- Abate by
- Oct 31, 2022
- Penalty
- Initial $9,136 · Current $5,500 Reduced
E200
General-duty citation text
29 CFR 1910.307(b): Areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007 were not properly documented: (a) Saw Room and other Production Areas: On or about December 10, 2021, the employer had not properly documented the locations, including the Saw Room, where combustible dusts are generated and other production areas where flammable and combustible products such as, but not limited to, paints and solvents are stored and used under the Class and Zone system.
Recent events (2)
- — I (S) $5500
- — Z (S) $9136
1910.307 C
- Issued
- Jun 9, 2022
- Abate by
- Jan 31, 2023
- Penalty
- Initial $0 · Current $0
E200
General-duty citation text
29 CFR 1910.307(c):Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) Saw Room and other Production Areas: On or about December 10, 2021, employees were working in an area with buildup of combustible dust where there were open motor fans, electrical outlet boxes, breaker panels, disconnect switches, normal lighting snap switches, overhead lighting, and control panels which were within a Class II, Division 1 location, were not intrinsically safe, and were not approved for a Class II, Division I location or safe for Class II, Division 1 locations. b) Saw Room and other Production Areas: On or about December 10, 2021, a vacuum was being used by employees in a Class II, Division 1 location, it was not intrinsically safe, and it was not approved for the Class II, Division 1 location or Safe for Class II, Division 1, locations.
Recent events (3)
- — P (S) $0
- — I (S) $0
- — Z (S) $0
1910.307 C02 I
- Issued
- Jun 9, 2022
- Abate by
- Jan 31, 2023
- Penalty
- Initial $0 · Current $0
E200
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of dust, that was or could be present: (a) Other Production and Storage Areas: On or about December 10, 2021, employees were working in an area with buildup of combustible dust where there were open motor fans, electrical outlet boxes, breaker panels, disconnect switches, normal lighting snap switches, overhead lighting, and control panels within a Class II, Division 2, location which were not intrinsically safe and were not approved for a Class II, Division 2 location or safe for Class II, Division 2 locations. (b) Other Production and Storage Areas: On or about December 10, 2021, a vacuum used in a Class II, Division 2 location was not intrinsically safe, approved for the Class II, Division 2 location or safe for Class II, Division 2 locations.
Recent events (3)
- — P (S) $0
- — I (S) $0
- — Z (S) $0
1904.10 A
- Issued
- Jun 9, 2022
- Abate by
- Jul 13, 2022
- Penalty
- Initial $1,305 · Current $1,000 Reduced
General-duty citation text
29 CFR 1904.10(a):The employer did not record all cases on the OSHA 300 Log when an employee's hearing test (audiogram) revealed that the employee had experienced a work-related Standard Threshold Shift (STS) in hearing in one or both ears, and the employee's total hearing level is 25 decibels (dB) or more above audiometric zero (averaged at 2000, 3000, and 4000 Hz) in the same ear(s) as the STS. (a) Facility wide: On or about December 15, 2021, the employer did not record all cases on the OSHA 300 Log when an employee's hearing test (audiogram) revealed that the employee had experienced a work-related Standard Threshold Shift (STS) in hearing in one or both ears, and the employee's total hearing level is 25 decibels (dB) or more above audiometric zero (averaged at 2000, 3000, and 4000 Hz) in the same ear(s) as the STS. The following three employees had not been recorded: 1. Establishment: Employee number 1 (Saw Room) suffered a Standard Threshold Shift 11.7 dB with a hearing level of 36 dB when averaged at 2000, 3000, and 4000 Hz range in the right ear and had not been recorded on the year 2021 OSHA 300 and 300A. 2. Establishment: Employee number 2 (Production) sustained a Standard Threshold Shift of 16.7 dB with a hearing level of 25 dB when averaged at 2000, 3000, and 4000 Hz range in the right ear and had not been recorded on the year 2021 OSHA 300 and 300A. 3. Establishment: Employee number 3 (Production) sustained a Standard Threshold Shift of 18.3 dB with a hearing level of 63 dB when averaged at 2000, 3000, and 4000 Hz range in the left ear and had not been recorded on the year 2021 OSHA 300 and 300A.
Recent events (2)
- — I (O) $1000
- — Z (O) $1305
1910.95 G08 I
- Issued
- Jun 9, 2022
- Abate by
- Jul 13, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.95(g)(8)(i): When a comparison of the annual audiogram to the baseline audiogram indicates a standard threshold shift, as defined in 29 CFR 1910.95(g)(10) has occurred, the employee was not informed of this fact in writing, within 21 days of the determination: (a) Facility wide: On or about August 12, 2021, when a comparison of the annual audiogram to the baseline audiogram on July 12, 2021 indicated a Standard Threshold Shift, as defined in 29 CFR 1910.95(g)(10) had occurred the employer did not inform the employees of this fact in writing, within 21 days of the determination for the following 3 employees: 1.Employee number 1 (Saw Room) suffered an STS 11.7 dB with a hearing level of 36 dB when averaged at 2000, 3000, and 4000 Hz range in the right ear. 2. Employee number 2 (Production) suffered an STS of 16.7 dB with a hearing level of 25 dB when averaged at 2000, 3000, and 4000 Hz range in the right ear. 3. Employee number 3 (Production) suffered an STS of 18.3 dB with a hearing level of 63 dB when averaged at 2000, 3000, and 4000 Hz range in the left ear.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at PCL Fixtures, INC.
View PCL Fixtures, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 337215)
More inspections in RI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345688451.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.