Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LINEAGE LOGISTICS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of LINEAGE LOGISTICS in 263 WEST KENSINGER DRIVE, CRANBERRY TOWNSHIP, PA 16066 (NAICS 493120). OSHA activity number 345700801.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Lineage Logistics — free Get an email when a new federal OSHA severe-injury report for Lineage Logistics is published. One employer, no account, unsubscribe in one click.
Establishment
LINEAGE LOGISTICS
Site address
263 WEST KENSINGER DRIVE
City
CRANBERRY TOWNSHIP
State
PA
ZIP
16066
Mailing
263 WEST KENSINGER DRIVE, CRANBERRY TOWNSHIP, PA 16066
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
20
Ownership type
A

8 citations on file for this inspection.

1910.119 D03 II

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 22, 2022
Abate by
Oct 27, 2022
Penalty
Initial $14,502 · Current $12,000 Reduced
29 CFR  1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices:   a)  In the Machinery Room, on or about December 22, 2021 - The employer did not document that equipment complied with Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) such as IIAR 2 (2014) Standards for Safe Design of Closed-Circuit Ammonia Refrigeration Systems Section 6.7 when employees did not have access to an eyewash/safety shower unit located inside the machinery room.  The facility maintenance mechanic performs work in the machinery room.  Failure to provide an accessible eyewash/safety shower in the Machinery Room can expose employees to serious eye damage and severe burns following skin contact.
Recent events (2)
  • — I (S) $12000
  • — Z (S) $14502

1910.119 D03 I E

Serious Gravity 5 1 instance 20 exposed
Issued
Jun 22, 2022
Abate by
Jun 30, 2023
Penalty
Initial $10,360 · Current $0 Reduced
29 CFR  1910.119(d)(3)(i)(E): Information pertaining to the equipment in the process did not include a ventilation system design:  a)  In the Machinery Room, on or about December 22, 2021 - The employer did not document ventilation system design basis, such as but not limited to applicable codes and standards, methods used to determine the maximum rate that the ventilation system must exhaust (e.g., cubic feet per minute (cfm)) for both emergency and non-emergency ventilation systems, and the supporting calculations for the ventilation system.  The unexpected release of anhydrous ammonia or a loss of air circulation could result in the accumulation of ammonia vapors inside the machinery room exposing employees to fire, explosion, and inhalation hazards.
Recent events (4)
  • — P (S) $0
  • — P (S) $0
  • — I (S) $0

1910.119 F01 I D

Serious Gravity 10 3 instances 1 exposed
Issued
Jun 22, 2022
Abate by
Feb 28, 2023
Penalty
Initial $14,502 · Current $12,000 Reduced
29 CFR  1910.119(f)(1)(i)(D): The employer did not develop and implement written operating procedures that provide clear instructions for emergency shutdown, including the conditions under which emergency shutdown is required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner:  a) In the Machinery Room, on or about December 22, 2021 - The employer did not develop and implement written operating procedures that provide clear instructions for the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner for the recirculators in Recirculator Operations.  Failure to assign shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner can expose employees to fire and toxic hazards.  b) In the Machinery Room, on or about December 22, 2021 - The employer did not develop and implement written operating procedures that provide clear instructions for the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner for the compressors in Compressor Operating Procedures and Deviation Recovery. Failure to assign shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner can expose employees to fire and toxic hazards.  c) On the Machinery Room Roof, on or about December 22, 2021 - The employer did not develop and implement written operating procedures that provide clear instructions for the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner for the evaporative condensers in Evaporative Condensers. Failure to assign shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner can expose employees to fire and toxic hazards.
Recent events (3)
  • — P (S) $12000
  • — I (S) $12000
  • — Z (S) $14502

1910.119 F01 III B

Serious Gravity 10 3 instances 1 exposed
Issued
Jun 22, 2022
Abate by
Feb 28, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.119(f)(1)(iii)(B): The employer did not develop and implement written operating procedures that included safety and health precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment.   a) In the Machinery Room, on or about December 22, 2021 - The employer did not develop and implement written operating procedures that included safety and health precautions necessary to prevent exposure during the task of a high liquid level event in Recirculator vessel, Recirculator Operations, including engineering controls, administrative controls, and personal protective equipment. Failure to include safety and health precautions in operating procedures can expose employees to fire and toxic hazards.  b) In the Machinery Room, on or about December 22, 2021 - The employer did not develop and implement written operating procedures that included safety and health precautions necessary to prevent exposure during the tasks of Manual Start-Up Procedures for the compressor and Manual Shut down procedures for the compressor, Compressor Operating Procedures and Deviation Recovery, including engineering controls, administrative controls, and personal protective equipment. Failure to include safety and health precautions in operating procedures can expose employees to fire and toxic hazards.  c) On the Machinery Room Roof, on or about December 22, 2021 - The employer did not develop and implement written operating procedures that included safety and health precautions necessary to prevent exposure during the task of Manual Start-Up Procedures for the evaporative condensers, Evaporative Condensers, including engineering controls, administrative controls, and personal protective equipment. Failure to include safety and health precautions in operating procedures can expose employees to fire and toxic hazards
Recent events (3)
  • — P (S) $0
  • — I (S) $0
  • — Z (S) $0

1910.119 F01 III C

Serious Gravity 10 3 instances 1 exposed
Issued
Jun 22, 2022
Abate by
Feb 28, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.119(f)(1)(iii)(C): The employer failed to ensure that the Process Safety Management Standard Operating Procedures included safety and health consideration such as control measures to be taken if physical contact or airborne exposure occurs:   a) In the Machinery Room, on or about December 22, 2021 - The employer's operating procedure titled Recirculator Operations, did not list the steps to be taken by the operators/mechanics if physical contact or airborne exposure to anhydrous ammonia occurs. Failure to include these steps in the operating procedures can result in insufficient knowledge and inadequate protection of employees during a release.  b) In the Machinery Room, on or about December 22, 2021 - The employer's operating procedure titled Compressor Operating Procedures and Deviation Recovery, did not list the steps to be taken by the operators/mechanics if physical contact or airborne exposure to anhydrous ammonia occurs. Failure to include these steps in the operating procedures can result in insufficient knowledge and inadequate protection of employees during a release.  c) On the Machinery Room Roof, on or about December 22, 2021 - The employer's operating procedure titled Evaporative Condensers, did not list the steps to be taken by the operators/mechanics if physical contact or airborne exposure to anhydrous ammonia occurs. Failure to include these steps in the operating procedures can result in insufficient knowledge and inadequate protection of employees during a release.
Recent events (3)
  • — P (S) $0
  • — I (S) $0
  • — Z (S) $0

1910.119 F03

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 22, 2022
Abate by
Jun 15, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.119(f)(3): The employer did not annually certify that operating procedures were current and accurate:  a) In the facility, on or about December 22, 2021 - The employer did not annually certify that operating procedures were current and accurate. Failure to annually certify that operating procedures for their anhydrous ammonia refrigeration system are current and accurate can expose employees to fire and toxic hazards.
Recent events (4)
  • — P (S) $0
  • — P (S) $0
  • — I (S) $0

1910.119 J02

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 22, 2022
Abate by
Feb 28, 2023
Penalty
Initial $14,502 · Current $0 Reduced
29 CFR  1910.119(j)(2): The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment:   a) In the facility, on or about December 22, 2021 - The employer did not establish and implement procedures to maintain the on-going integrity of process equipment, when the written procedures did not include procedures for visually inspecting insulated ammonia vessels, such as but not limited to -49-degree Recirculator Vessel; -28-degree Recirculator Vessel; and +15-degree Recirculator Vessel for damage and/or moisture inside insulation and procedures for testing vessel at area where insulation degradation may be observed.  Failure to inspect, test and maintain insulated ammonia vessels can lead to loss of containment and exposure to toxic vapors and fire hazards.  b) In the facility, on or about December 22, 2021 - The employer did not establish and implement procedures to maintain the on-going integrity of process equipment, when the written procedures did not include procedures for visually inspecting insulated ammonia piping, such as but not limited to high temperature recirculated suction; low temperature recirculated suction; high temperature recirculated liquid; high gas defrost; and low temperature recirculated liquid for damage and/or moisture inside insulation and procedures for testing piping at area where insulation degradation may be observed.  Failure to inspect, test and maintain insulated ammonia piping can lead to loss of containment and exposure to toxic vapors and fire hazards.
Recent events (3)
  • — P (S) $0
  • — I (S) $0
  • — Z (S) $14502

1910.119 O01

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 22, 2022
Abate by
Aug 26, 2022
Penalty
Initial $14,502 · Current $12,000 Reduced
29 CFR  1910.119(o)(1): The employer did not certify that they have evaluated compliance with the provisions of this section at least every three years:  a) In the facility, on or about December 22, 2021 - The employer failed to certify that they have evaluated compliance with the provisions of this section at least every three years. The most recent compliance audit was conducted in 2013.  Failure to evaluate that their procedures and practices for their anhydrous ammonia refrigeration system are in compliance with the provisions of this section every three years can expose employees to fire and toxic hazards.
Recent events (2)
  • — I (S) $12000
  • — Z (S) $14502

View Lineage Logistics's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345700801.