BAYTOWN, TX —
OSHA Inspection: EXXON MOBIL BAYTOWN REFINERY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of EXXON MOBIL BAYTOWN REFINERY in 2800 DECKER DR., BAYTOWN, TX 77520 (NAICS 324110). OSHA activity number 345702757.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EXXON MOBIL BAYTOWN REFINERY
- Site address
- 2800 DECKER DR.
- City
- BAYTOWN
- State
- TX
- ZIP
- 77520
- Mailing
- 2800 DECKER DR., BAYTOWN, TX 77520
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 1300
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.119 J02
- Issued
- Jun 3, 2022
- Abate by
- Jul 22, 2022
- Penalty
- Initial $14,502 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): Written procedures. The employer shall establish and implement written procedures to maintain the on-going integrity of process equipment. On or about December 23, 2021, in Hydro Desulfurization Unit (HDU-1) at ExxonMobil refinery located in Baytown, TX, the employer did not implement its established written procedure "Stagnant zone and Dead leg inspection data procedure", to assign the Thickness Measurement Locations (TMLs) on the 14-inch bypass pipe of reactor R-701.
Recent events (2)
- — I (S) $0
- — Z (S) $14502
1910.119 J04 I
- Issued
- Jun 3, 2022
- Abate by
- Jul 22, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(j)(4)(i) Inspections and tests were not performed on process equipment. On or about December 23, 2021, in Hydro Desulfurization Unit (HDU-1) at Exxon Mobil refinery located in Baytown, TX, the employer failed to perform inspection and test on and test on the 14-inch process bypass pipe (line# 0-084-300*-*) of reactor R-701.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.39 C01
- Issued
- Jun 3, 2022
- Abate by
- Oct 3, 2022
- Penalty
- Initial $14,502 · Current $14,502
General-duty citation text
1910.39(c)(1) A fire prevention plan did not include: A list of all major fire hazards, proper handling and storage procedures for hazardous materials, potential ignition sources and their control, and the type of fire protection equipment necessary to control each major hazard; On or about December 23, 2021, in the Hydro Desulfurization Unit (HDU-1), at ExxonMobil Refinery in Baytown, Texas, the employer did not identify and anticipate the potential for re-ignition following application of steam lances and select personal of personal protective equipment to be used by employees that would protect them against the potential for re-ignition while assessing a naphtha leak.
Recent events (2)
- — I (S) $14502
- — Z (S) $14502
1910.165 B05
- Issued
- Jun 3, 2022
- Abate by
- Aug 31, 2022
- Penalty
- Initial $14,502 · Current $14,502
General-duty citation text
1910.165(b)(5) The employer did not implement its procedure for sounding emergency alarms in the workplace. On or about December 23, 2021, in Hydro Desulfurization Unit (HDU-1) at ExxonMobil refinery located in Baytown, TX, the unit alarm was not activated during an emergency event.
Recent events (2)
- — I (O) $14502
- — Z (S) $14502
1910.120 Q03 V
- Issued
- Jun 3, 2022
- Abate by
- Sep 30, 2022
- Penalty
- Initial $14,502 · Current $14,502
General-duty citation text
1910.120(q)(3)(v) The individual in charge of the ICS did not limit the number of emergency response personnel at the emergency site, in those areas of potential or actual exposure to incident or site hazards, to those who are actively performing emergency operations. However, operations in hazardous areas shall be performed using the buddy system in groups of two or more. On or about December 23, 2021, employees at ExxonMobil Refinery in Baytown, Texas, not all responding employee personnel used the buddy system to be accompanied by ERT personnel when entering the unit during an emergency to isolate/close valves in order to block-in fuel after certain remote operated valves became inoperable as a result of a fire.
Recent events (2)
- — I (S) $14502
- — Z (S) $14502
1910.120 Q02 XI
- Issued
- Jun 3, 2022
- Abate by
- Jul 22, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.120(q)(2)(xi): Proper PPE were not used for emergency response. On or about December 23, 2021, in the Hydro Desulfurization Unit (HDU-1) at ExxonMobil Refinery in Baytown, Texas, the employer did not ensure outside operators attempting to isolate the unit at the south side battery limits were in proper PPE.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.132 D01
- Issued
- Jun 3, 2022
- Abate by
- Jun 23, 2022
- Penalty
- Initial $14,502 · Current $0 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards were present, or were likely to be present, which necessitated the use of personal protective equipment: On or about December 22, 2021, in the the Hydro Desulfurization Unit (HDU-1)at ExxonMobil Refinery in Baytown, Texas, the employer failed to perform an adequate assessment to determine and address the workplace and did not select and have employees and contractors use personal protective equipment that would protect them in the event of a fire while working on/near a Naphtha flange leak.
Recent events (2)
- — I (S) $0
- — Z (S) $14502
1910.119 D03 I B
- Issued
- Jun 3, 2022
- Abate by
- Jul 22, 2022
- Penalty
- Initial $1,163 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): Process Safety Information pertaining to the piping and instrumentation diagrams (P&ID) was not compiled, complete and accurate. This violation was most recently observed on or about December 23, 2021, in Hydro Desulfurization Unit (HDU-1) at ExxonMobil refinery located in Baytown, TX, when the employer did not ensure Process Safety Information (PSI) such as Piping and Instrumentation Diagram (P&ID) # 134-500-0058, Rev 4, was complete and accurate included, but not limited to the following: a. 14-inch flanges were missing on a bypass line from furnace F-701 to reactor R-702B. b. Line number 0-084-14"-300# was missing for 14-inch bypass line. c. Normally closed (NC) symbols were missing for valves ROV-075 and ROV-605.
Recent events (2)
- — I (O) $0
- — Z (O) $1163
More inspections at Exxon Mobil Baytown Refinery
View Exxon Mobil Baytown Refinery's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345702757.