MILTON, PA —
OSHA Inspection: WEIS MARKETS INCORPORATED
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of WEIS MARKETS INCORPORATED in 16 SOUTH INDUSTRIAL PARK ROAD, MILTON, PA 17847 (NAICS 493120). OSHA activity number 345748180.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WEIS MARKETS INCORPORATED
- Site address
- 16 SOUTH INDUSTRIAL PARK ROAD
- City
- MILTON
- State
- PA
- ZIP
- 17847
- Mailing
- 16 SOUTH INDUSTRIAL PARK ROAD, MILTON, PA 17847
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 345
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.119 D03 II
- Issued
- Jul 21, 2022
- Abate by
- Aug 16, 2022
- Penalty
- Initial $8,806 · Current $0 Reduced
0170
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: a) 16 South Industrial Park Road, Milton, PA: Engine room - the employer did not document that equipment complies with the employer's chosen RAGAGEP such as IIAR 2 -2014 Standard for Safe Design of Closed-Circuit Ammonia Refrigeration Systems, Section 6.2.1 in that a plastic vent pipe connected the adjacent Workshop-Storage Room and Engine Room through an opening in the shared wall. Failure of the ventilation system or fire suppression system in the engine room could expose employees in the Workshop-Storage room to smoke, fire and anhydrous ammonia, on or about March 25, 2022. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $8806
1910.119 E03 V
- Issued
- Jul 21, 2022
- Abate by
- Aug 16, 2022
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address the hazards related to facility siting: a) 16 South Industrial Park Road, Milton, PA: Engine room - the process hazard analysis did not address the potential for spread of fire between the adjacent Workshop-Storage Room and Engine Room through a vent opening in the shared wall. Failure to stop the spread of fire could expose employees to smoke and fire resulting in smoke inhalation, burns or death on or about March 25, 2022. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F04
- Issued
- Jul 21, 2022
- Abate by
- Aug 16, 2022
- Penalty
- Initial $8,806 · Current $0 Reduced
0170
General-duty citation text
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel: a) 16 South Industrial Park Road, Milton, PA: Refrigeration System - the employer did not develop and implement safe work practices to provide for the control of hazards during operations of the Banana Glycol Chiller such as a car seal program to ensure that the isolation valve (HV90-15) on the discharge PSV (90-14) was car sealed or locked open during operations of the Banana Room Glycol Chiller. Failure to establish clear procedures for inspecting the car-sealed valve could result in failure of the valve or over-pressurization of the chiller exposing employees to anhydrous ammonia on or about March 24, 2022. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $8806
1910.119 J02
- Issued
- Jul 21, 2022
- Abate by
- Aug 16, 2022
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not implement written procedures to maintain the on-going integrity of process equipment: a) 16 South Industrial Park Road, Milton, PA: Refrigeration System - The employer failed to establish and implement written procedures to maintain the on-going integrity of the Banana Glycol Chiller such as a car seal program to ensure that the isolation valve (HV90-15) on the discharge PSV (90-14) was able to readily and effectively controlled during all planned and unplanned maintenance on the Banana Room Glycol Chiller. Failure to establish clear procedures for maintaining the car-sealed valve could result in failure of the valve or over-pressurization of the chiller exposing employees to anhydrous ammonia on or about March 24, 2022. b) 16 South Industrial Park Road, Milton, PA: Refrigeration System - The employer failed to establish and implement written procedures to maintain the on-going integrity of the Frick high pressure receiver (HPR). Failure to conduct inspections to detect corrosion under insulation could result in a loss of containment exposing employees to anhydrous ammonia on or about March 25, 2022. c) 16 South Industrial Park Road, Milton, PA: Refrigeration System - The employer failed to establish and implement written procedures to maintain the on-going integrity of the Frick high temperature recirculator (HTPR1). Failure to conduct inspections to detect corrosion under insulation could result in a loss of containment exposing employees to anhydrous ammonia on or about March 25, 2022. d) 16 South Industrial Park Road, Milton, PA: Refrigeration System - The employer failed to establish and implement written procedures to maintain the on-going integrity of the RVS low temperature recirculator (LTPR2). Failure to conduct inspections to detect corrosion under insulation could result in a loss of containment exposing employees to anhydrous ammonia on or about March 25, 2022. e) 16 South Industrial Park Road, Milton, PA: Refrigeration System - The employer failed to establish and implement written procedures to maintain the on-going integrity of the RVS thermosyphon (TSV). Failure to conduct inspections to detect corrosion under insulation could result in a loss of containment exposing employees to anhydrous ammonia on or about March 25, 2022. f) 16 South Industrial Park Road, Milton, PA: Refrigeration System - The employer failed to establish and implement work procedures to provide for the control of hazards during maintenance of the Hansen Auto Purger Plus APP16. Failure to establish clear procedures for maintaining the electrical solenoid-controlled valves could result in improper repair which could result in a loss of containment exposing employees to anhydrous ammonia on or about March 25, 2022. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 L05
- Issued
- Jul 21, 2022
- Abate by
- Aug 16, 2022
- Penalty
- Initial $8,806 · Current $0 Reduced
0170
General-duty citation text
29 CFR 1910.119(l)(5): A change covered by this paragraph resulted in a change in the operating procedures or practices required by paragraph (f) of this section, and such procedures or practices were not updated accordingly: a) 16 South Industrial Park Road, Milton, PA: Refrigeration System - operating practices for the use of the Hansen Auto Purger Plus APP16 were changed from automatic to manual actuation and the written operating procedures were not updated to reflect the changes. Improper operation of the purger could create stressors to the refrigeration system and purger which could result in a loss of containment exposing employees to anhydrous ammonia on or about March 25, 2022. ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $8806
1910.119 D03 I F
- Issued
- Jul 21, 2022
- Abate by
- Aug 16, 2022
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(d)(3)(i)(F): Information pertaining to the equipment in the process did not include design codes and standards that were employed: a) 16 South Industrial Park Road, Milton, PA: Refrigeration System: Information pertaining to the equipment in the process such as compressors, piping and pressure vessels did not include design codes and standards that were employed to inspect for corrosion under insulation. Failure to document standards used for inspection and testing can lead to inadequate equipment inspections, component failures and exposure to anhydrous ammonia, on or about March 25, 2022 ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Weis Markets Incorporated
View Weis Markets Incorporated's full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345748180.