PHOENIX, AZ —
OSHA Inspection: AZ ARMY NATIONAL GUARD-CSMS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of AZ ARMY NATIONAL GUARD-CSMS in 1301 N 52ND STREET, PHOENIX, AZ 85008 (NAICS 561210). OSHA activity number 345748461.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AZ ARMY NATIONAL GUARD-CSMS
- Site address
- 1301 N 52ND STREET
- City
- PHOENIX
- State
- AZ
- ZIP
- 85008
- Mailing
- 1301 N 52ND STREET, PHOENIX, AZ 85008
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 46
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Feb 8, 2022
- Abate by
- Feb 18, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) SASMO: A 15A Tripp lite relocatable power tap and black extension cord were "daisy chained", exposing employees to electrical shock hazards.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Feb 8, 2022
- Abate by
- Feb 18, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a)SASMO: Extension cords were used to provide power to the e800 satellite modem #742T and 2 relocatable power taps, exposing employees to electrical shock and fire hazards.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Feb 8, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii):Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) AUTOMOTIVE SHOP BAY 7: A 20 foot extension cord was not provided with strain relief, and the outer jacket had separated from the plug at the female end, exposing employees to electrical hazards. b) COMM SHOP: A six foot extension cord was not provided with strain relief, and the outer jacket had separated from the plug at the female end, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
More inspections at AZ Army National Guard-Csms