FORT RICHARDSON, AK —
OSHA Inspection: ARMY NATIONAL GUARD FOC BUILDING 47420 FORT RICHARDSON, AK 99505
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY NATIONAL GUARD FOC BUILDING 47420 FORT RICHARDSON, AK 99505 in BUILDING 47420 EXTENSION, FORT RICHARDSON, AK 99505 (NAICS 928110). OSHA activity number 345775332.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- BUILDING 47420 EXTENSION
- City
- FORT RICHARDSON
- State
- AK
- ZIP
- 99505
- Mailing
- ATTN: LT. COL. DAN KELLER BUILDING 49140 ARMY GUARD RD., JBER, AK 99505
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 85
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.215 A01
- Issued
- Jul 20, 2022
- Abate by
- Aug 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(1): Abrasive wheel(s) used on grinding machinery were not used with safety guard(s): a) Room 112: On or about January 9, 2022, a Wen WEN 4276 2.1 Amp Motor -6 Inch Bench Grinder 3450 RMP 6"x3/4 Inch wheels, 1/2 arbor was missing a guard exposing employees to caught-in and struck by hazards.
Recent events (1)
- — Z (S) $0
1910.253 B04 I
- Issued
- Jul 20, 2022
- Abate by
- Aug 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire: a) Hanger adjacent to electrical panel #36: On or about January 9, 2022, Several M-Cylinder Oxygen tanks were stored improperly and in close proximity to an electrical panel, cleaning supplies and mounted to a screen fence with a truckers tiedown, exposing employees to explosions, fire, and burn hazards.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Jul 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Room 112: On or about January 9, 2022, a relocatable power tap (surge protector) was permanently mounted to the wall of a filing cabinet subjecting employees to fire and electrical shock hazards. b) Building 47430 Admin Area: On or about January 9, 2022, a Relocatable Power Tap was used in conjunction with another extension cable creating an electrical hazard, exposing employees to electrical shock and fire.
Recent events (1)
- — Z (S) $0
1910.303 G01 I B
- Issued
- Jul 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels. a) Hanger Panel #36: On or about February 9, 2022, several oxygen cylinders were stored in front of an electrical panel restricting the working space that did not allow the panel be readily accessible in the event of an critical emergency, exposing employees to electrical hazards. b) Near or Room 100: On or about February 9, 2022, a maintenance lift, broom, and a box of ice melt was stored in front of an electrical panel restricting the working space and did not allow the panel be readily accessible in the event of an electrical emergency, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Jul 20, 2022
- Abate by
- Aug 1, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Vehicle Parking Yard: On or about January 9, 2022, Several outlet covers were either missing or out of service exposing employees to electrical shock hazards.
Recent events (1)
- — Z (S) $0
More inspections at Army National Guard FOC Building 47420 Fort Richardson, AK 99505
View Army National Guard FOC Building 47420 Fort Richardson, AK 99505's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345775332.