Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KINDEN CORPORATION

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of KINDEN CORPORATION in BUILDING A, FRC HOMEPORT SECTOR, UNITED STATES COAST GUARD GUAM NAVAL BASE, SANTA RITA, GU 96915 (NAICS 236210). OSHA activity number 345869424.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kinden Corporation — free Get an email when a new federal OSHA severe-injury report for Kinden Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
KINDEN CORPORATION
Site address
BUILDING A, FRC HOMEPORT SECTOR, UNITED STATES COAST GUARD GUAM NAVAL BASE
City
SANTA RITA
State
GU
ZIP
96915
Mailing
PO BOX 9609, TAMUNING, GU 96931
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236210
Employees
15
Ownership type
A

3 citations on file for this inspection.

1926.95 A

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 23, 2022
Abate by
Jul 6, 2022
Penalty
Initial $13,052 · Current $11,747 Reduced
29 CFR  1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided:  On March 31, 2022, in the ceiling above Vestibule A, an employee troubleshooting live electrical parts at 277/480 volts was not provided with voltage rated insulating rubber gloves.  Employee was exposed to electrical hazards.
Recent events (2)
  • — I (S) $11746.7
  • — Z (S) $13052

1926.416 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 23, 2022
Abate by
Jul 6, 2022
Penalty
Initial $13,052 · Current $11,747 Reduced
29 CFR  1926.416(a)(1): Employee(s) were permitted to work in proximity to electric power circuits that were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  On March 31, 2022, in the ceiling above Vestibule A, the power to the motion sensor power pack was not de-energized before an employee was assigned to troubleshoot the motion sensor lighting system.  Employee was exposed to electrical hazards.
Recent events (2)
  • — I (S) $11746.7
  • — Z (S) $13052

1904.39 A01

Other-than-serious 1 instance 1 exposed
Issued
Jun 23, 2022
Penalty
Initial $9,324 · Current $8,392 Reduced
29 CFR  1904.39(a)(1): Within eight (8) hours after the death of any employee as a result of a work-related incident, the employer did not report the fatality to the Occupational Safety and Health Administration (OSHA), U.S. Department of Labor.  On or about March 31, 2022, an employee was electrocuted and fell from a 6-foot ladder and was not reported until April 1, 2022, approximately 22 hours after learning of the fatality .
Recent events (2)
  • — I (O) $8391.6
  • — Z (O) $9324

View Kinden Corporation's full OSHA safety record →