Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BRILEX INDUSTRIES INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BRILEX INDUSTRIES INC. in 101 ANDREWS AVENUE, YOUNGSTOWN, OH 44503 (NAICS 332312). OSHA activity number 345883771.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Brilex Industries INC. — free Get an email when a new federal OSHA severe-injury report for Brilex Industries INC. is published. One employer, no account, unsubscribe in one click.
Site address
101 ANDREWS AVENUE
City
YOUNGSTOWN
State
OH
ZIP
44503
Mailing
101 ANDREWS AVENUE, YOUNGSTOWN, OH 44503
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
57
Ownership type
A

1 citation on file for this inspection.

1910.303 G01 I B

Serious Gravity 1 1 instance 1 exposed
Issued
May 3, 2022
Penalty
Initial $4,351 · Current $4,351
29 CFR  1910.303(g)(1)(i)(B):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater   On or about April 07, 2022: the employer did not ensure that the width of working space in front of electrical equipment was greater than 30 inches. Electrical boxes were mounted within 17 inches of a steel beam in the fabrication area exposing employees to electrical hazards in the following instances:  a)	The front area of a Siemens 480V electrical box used to power an exhaust fan was blocked by a structural steel beam. The electrical box was mounted within 17 inches of steel beam.   b)	The front area of a Square D 480V electrical box used to power an exhaust fan was blocked by a structural steel beam. The electrical box was mounted within 17 inches of steel beam.
Recent events (1)
  • — Z (S) $4351

View Brilex Industries INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345883771.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.