Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TURN KEY UTILITY CONSTRUCTION, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TURN KEY UTILITY CONSTRUCTION, INC. in ADJACENT 9377 N WAKEFIELD RD., JUSTIN, TX 76247 (NAICS 237110). OSHA activity number 345917330.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Turn KEY Utility Construction, INC. — free Get an email when a new federal OSHA severe-injury report for Turn KEY Utility Construction, INC. is published. One employer, no account, unsubscribe in one click.
Site address
ADJACENT 9377 N WAKEFIELD RD.
City
JUSTIN
State
TX
ZIP
76247
Mailing
9716 LIMESTONE CT., JOSHUA, TX 76058
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237110
Employees
40
Ownership type
A

11 citations on file for this inspection.

1910.67 C03

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $8,702 · Current $5,221 Reduced
29 CFR  1910.67(c)(3): Electrical tests had not been made in conformance with the requirements of ANSI A92.2-1969, Section 5:  On or about March 22, 2022, and at time prior thereto electrical test were not conducted on the bucket truck prior to performing work on electrical system.
Recent events (2)
  • — I (S) $5221.2
  • — Z (S) $8702

1910.157 C04

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $4,351 · Current $2,611 Reduced
29 CFR  1910.157(c)(4):The employer did not assure that portable fire extinguishers are maintained in a fully charged and operable condition and kept in their designated places at all times except during use.  On or about March 22, 2022, and at times prior thereto, the portable fire extinguisher was not fully charged, in operable condition and kept in its designated place on the bucket truck.
Recent events (2)
  • — I (S) $2610.6
  • — Z (S) $4351

1910.157 G03

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.157(g)(3):The employer did not provide employees who have been designated to use fire fighting equipment as part of an emergency action plan with training in the use of the appropriate equipment.  On or about March 22, 2022, and at times prior thereto, employees who have been designated to use fire extinguishers were not trained.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 B01 I

Serious Gravity 10 1 instance 4 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $10,151 · Current $6,091 Reduced
29 CFR  1910.269(b)(1)(i): When two or more employees were performing field work on, or associated with, exposed lines or equipment energized at 50 volts or more, the employer did not provide at least two trained persons with first-aid training.  On or about March 22, 2022, and at times prior thereto, employees conducted mobile electrical field work, with no one onsite trained or certified in first-aid (CPR) training.
Recent events (2)
  • — I (S) $6090.6
  • — Z (S) $10151

1910.269 L02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $10,151 · Current $6,091 Reduced
29 CFR  1910.269(l)(2)(i): Except as provided in paragraph (l)(2)(ii) of this section, at least two employees were not present while any employees perform the following types of work: (A) Installation, removal, or repair of lines energized at more than 600 volts, (B) Installation, removal, or repair of deenergized lines if an employee is exposed to contact with other parts energized at more than 600 volts, (C) Installation, removal, or repair of equipment, such as transformers, capacitors, and regulators, if an employee is exposed to contact with parts energized at more than 600 volts, (D) Work involving the use of mechanical equipment, other than insulated aerial lifts, near parts energized at more than 600 volts, and (E) Other work that exposes an employee to electrical hazards greater than, or equal to, the electrical hazards posed by operations listed specifically in paragraphs (l)(2)(i)(A) through (l)(2)(i)(D) of this section.   On or about March 22, 2022, and at times prior thereto, one employee was allowed to perform repair work on electrical lines exposing the employee to energized parts.
Recent events (2)
  • — I (S) $6090.6
  • — Z (S) $10151

1910.269 N03

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.269(n)(3):Equipotential zone. Temporary protective grounds were not placed at such locations and arranged in such a manner that the employer can demonstrate will prevent each employee from being exposed to hazardous differences in electric potential.  Note to paragraph (n)(3): Appendix C to this section contains guidelines for establishing the equipotential zone required by this paragraph. The Occupational Safety and Health Administration will deem grounding practices meeting these guidelines as complying with paragraph (n)(3) of this section.  On or about March 22, 2022, and at times prior thereto, temporary protective grounds were not installed to prevent employees from being exposed to a hazardous differences in electrical potential.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 N05

Serious Gravity 10 1 instance 3 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.269(n)(5): Testing. The employer did not ensure that, unless a previously installed ground is present, employees test lines and equipment and verify the absence of nominal voltage before employees install any ground on those lines or that equipment.  On or about March 22, 2022, and at times prior thereto,  it was not verified or determined through testing that electrical lines and equipment were absence of nominal voltage before employees installed any ground.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 L03 III

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:   On or about March 22, 2022, and at times prior thereto, the employer allowed employees to approach closer to exposed energized parts than the employer's established minimum approach distance (MAD), exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 L06 III

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.269(l)(6)(iii): When lines or equipment are connected to or disconnected from energized circuits, an employee did not keep loose conductors away from exposed energized parts.  On or about March 22, 2022, and at times prior thereto employees did not keep loose conductors away from exposed energized lines or parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.39 A02

Other-than-serious 1 instance 1 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $7,252 · Current $4,351 Reduced
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye:  The employer did not report an in-patient hospitalization that occurred on or about March 22, 2022,  at 4100 Block of Wakefield Rd, Justin TX within the required 24 hours after knowing of the hospitalization.  The injury was reported on March 31, 2022, via FOIA request from employee counsel.
Recent events (2)
  • — I (O) $4351.2
  • — Z (O) $7252

1910.269 D02 IX

Other-than-serious 1 instance 4 exposed
Issued
Aug 24, 2022
Abate by
Sep 15, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.269(d)(2)(ix): The employer did not certify that employee training has been accomplished and is being kept up to date. The certification did not contain each employee's name and dates of training.  On or about March 22, 2022, and at times prior thereto employee training had not been accomplished.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Turn KEY Utility Construction, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345917330.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.