MIDDLETON, ID —
OSHA Inspection: ALTITUDE ENERGY LLC
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of ALTITUDE ENERGY LLC in LANCING LANE AND FOOTHILLS RD, MIDDLETON, ID 83644 (NAICS 237130). OSHA activity number 345920870.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALTITUDE ENERGY LLC
- Site address
- LANCING LANE AND FOOTHILLS RD
- City
- MIDDLETON
- State
- ID
- ZIP
- 83644
- Mailing
- PO BOX 359, KEENESBURG, CO 80643
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 6
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Oct 25, 2022
- Abate by
- Dec 2, 2022
- Penalty
- Initial $13,052 · Current $11,095 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1) The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees from high voltage overhead powerlines: a) On April 25, 2022; pole anchor guy lines were not installed with guy insulators positioned below where the guy line could become energized by contact with 7.2kv overhead lines. Among other methods, feasible and acceptable means of abatement may include compliance with 2017 (or later) National Electrical Safety Code(R) (NESC(R)), IEEE C2-2017, Section 215. Anchor guys shall be effectively grounded, except where guy insulators are installed and positioned to limit the likelihood of any portion of an anchor guy becoming energized within 2.45 m (8 ft) of the ground level in the event that the anchor guy becomes, slack, breaks or otherwise contacts energized lines.
Recent events (2)
- — I (S) $11095
- — Z (S) $13052
More inspections at Altitude Energy LLC
View Altitude Energy LLC's full OSHA safety record →
More inspections in this industry (NAICS 237130)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345920870.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.