EIELSON AFB, AK —
OSHA Inspection: DEFENSE COMMISSARY AGENCY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DEFENSE COMMISSARY AGENCY in 2540 CENTRAL AVE STE. 100, EIELSON AFB, AK 99702 (NAICS 445110). OSHA activity number 346124084.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEFENSE COMMISSARY AGENCY
- Site address
- 2540 CENTRAL AVE STE. 100
- City
- EIELSON AFB
- State
- AK
- ZIP
- 99702
- Mailing
- 2540 CENTRAL AVENUE SUITE 100, EIELSON AFB, AK 99702
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 33
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.22 A02
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(2): The Floor of each workroom was not maintained in a clean and, to the extent feasible, in a dry condition. When wet process were used, mats were not provided. a) Meat Department: On or about August 3, 2022, cardboard was on the floor used as a non-slip surface and no mats when employees were cutting meat, exposing's employees to slip, trips, and or fall hazards.
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Dec 12, 2022
- Abate by
- Dec 27, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3) Exit routes were not free and/or unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. a) Meat Department: On or about August 3, 2022, the exit door was blocked by a storage room door that was left open, exposing the employees to a blocked exit route, fire hazard, and delayed egress.
Recent events (1)
- — Z (S) $0
1910.37 B04
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): The direction of travel to the exit or exit discharge was not immediately apparent, signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge. a) Meat Department: On or about August 3, 2022, exit sign was missing along the exit route to the nearest emergency exit door exposing employees to smoke inhalation and fire hazards.
Recent events (1)
- — Z (S) $0
1910.37 B05
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use. a) Meat Department: On or about August 3, 2022, "Not an Exit" sign was missing for a storage room door that could be mistaken for an exit exposing employees to smoke inhalation and fire hazards.
Recent events (1)
- — Z (S) $0
1910.303 B07 IV
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action or overheating. a) Meat Cutting Room: On or About August 3, 2022, an energized electrical panel connected to a Hobart Meat Hopper had a plastic bag wrapped around the top conduit, exposing employees to electrical and fire hazards. b) Meat Cutting Room: On or About August 3, 2022, an energized electrical panel connected to a Hobart Meat Grinder had a plastic bag wrapped around the top conduit, exposing employees to electrical and fire hazards. c) Meat Cutting Room: On or About August 3, 2022, an energized electrical panel that links both the grinder and the hopper together, was broken with scotch tape holding it together, exposing employees to electrical hazards. d) Meat Cutting Room: On or about August 3, 2022, a Hobart commercial meat saw had a single pull-to-start power switch, the switch does not stay in the 'On' position while in operations. This exposes employees to an unexpected start-up that could result in an amputation or laceration hazard.
Recent events (1)
- — Z (S) $0
1910.303 B08 I
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(8)(i): Electrical equipment was not firmly secured to the surface on which it was mounted. a) Meat Department: On or about August 3, 2022, an outlet receptacle was pulling away from the electrical box it was mounted in and electrical wiring was visible, exposing employees to electrical shock and fire hazards.
Recent events (1)
- — Z (S) $0
1910.303 G01 I B
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment was not the width of the equipment or 762 mm (30 in.), whichever is greater. a) Warehouse back admin area: On or about August 3, 2022, the working space in front of an electrical panel labeled 'Small Charger Panel' had a desk in front of it, exposing employee to electrical and fire hazards.
Recent events (1)
- — Z (S) $0
1960.8 A
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm: a) Warehouse: On or about August 3, 2022, employees performed material handling operations with six green industrial steel racking systems with boxes of items stored on the shelving. Interior, front and rear column baseplates on the frames of the racking system were not anchored to the floor to resist all applicable forces, exposing employees to struck-by and crushing hazard.
Recent events (1)
- — Z (S) $0
1910.157 E02
- Issued
- Dec 12, 2022
- Abate by
- Dec 20, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly. a) On or about August 3, 2022, a portable fire extinguisher was provided for employee use, but monthly visual inspections were not being performed, exposing employees to fire hazard.
Recent events (1)
- — Z (O) $0
More inspections at Defense Commissary Agency
View Defense Commissary Agency's full OSHA safety record →
More inspections in this industry (NAICS 445110)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346124084.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.