Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EATON CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EATON CORPORATION in 269 PARSONS AVE., MOUNTAIN VIEW, CA 94035 (NAICS 238210). OSHA activity number 346233687.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Eaton Corporation — free Get an email when a new federal OSHA severe-injury report for Eaton Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
EATON CORPORATION
Site address
269 PARSONS AVE.
City
MOUNTAIN VIEW
State
CA
ZIP
94035
Mailing
1000 EATON BLVD, BEACHWOOD, OH 44122
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
50000
Ownership type
A

2 citations on file for this inspection.

1926.961 C02

Serious Gravity 10 1 instance 4 exposed
Issued
Nov 30, 2022
Abate by
Dec 27, 2022
Penalty
Initial $12,327 · Current $12,327
29 CFR 1926.961(c)(2) Standard: Open disconnecting means. The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized were open. The employer rendered the means inoperable, unless its design did not so permit, and ensured that such means were tagged to indicate that employees were at work.  AVD: On September 13, 2022, the employer applied its locks to all switches and other means through which known sources of electric energy may be supplied to an electrical substation prior to commencing maintenance work, but erroneously applied its lock to one of the switches that remained in the closed position, thereby exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $12327
  • — Z (S) $12327

1926.961 C06

Serious Gravity 10 1 instance 6 exposed
Issued
Nov 30, 2022
Abate by
Dec 27, 2022
Penalty
Initial $12,327 · Current $0 Reduced
29 CFR 1926.961(c)(6) Standard: Test for energized condition. After the applicable requirements in paragraphs (c)(1) through (c)(5) of this section had been followed and the system operator gave a clearance to the employee in charge, the employer did not ensure that the lines and equipment were deenergized by testing the lines and equipment to be worked with a device designed to detect voltage.  AVD: On September 13, 2022 the employer tested the lines and equipment with a voltage proximity detector using the Live-Dead-Live method at an electrical substation prior to commencing maintenance work, but failed to test the equipment in one cell on the back side of the substation, which was erroneously believed to be outside the arc flash boundary, thereby exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $12327

View Eaton Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346233687.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.