OSHA Inspection: PATTEN RESERVE CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PATTEN RESERVE CENTER in 5340 BANDINI BLVD BUILDING 1, BELL, CA 90201 (NAICS 928110). OSHA activity number 346259617.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Patten Reserve Center — free Get an email when a new federal OSHA severe-injury report for Patten Reserve Center is published. One employer, no account, unsubscribe in one click.
Site address
5340 BANDINI BLVD BUILDING 1
City
BELL
State
CA
ZIP
90201
Mailing
5340 BANDINI BLVD, BELL, CA 90201
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
10
Ownership type
D

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 7 instances 7 exposed
Issued
Nov 16, 2022
Abate by
Feb 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or before October 3, 2022, Employee(s) used refrigerator, microwave and coffee maker appliance daily to store and heat consumable goods for consumption. The refrigerator, microwave, and coffee maker appliances were plugged into power taps and/or into temporary extension cords and were not used according to the listing and labeling instructions. Employee(s) were exposed to electrical shock and/or fire hazard(s).   In the following locations:  (a) Room 112 - Fridge, Coffee Maker, and microwave plugged into a relocatable power tap. (b) Room 113 - Adjustable pedestal fan plugged into a relocatable power tap. (c) Room 104A - Coffee Maker, microwave, and two toasters plugged into a relocatable power tap. (d) Room 105 - A - A temporary extension cord was plugged into a relocatable power tap. (e) Room 118 - Coffee Maker, microwave, two adjustable pedestal fans and one table fan plugged into relocatable power tap. (f) Room 201 - Multiple relocatable power taps were daisy chained. (g) Room 204 - HP printer and a portable ceramic air heater plugged into a relocatable power tap.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 2 instances 1 exposed
Issued
Nov 16, 2022
Abate by
Dec 6, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  On or Before October 3, 2022, the employer permitted materials to be stored directly in front of the electrical panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition exposed employees to an electrical and/or fire hazard(s).    In the following locations: (a) Room 113  (b) Room 106
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 16, 2022
Abate by
Feb 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  Building 1, Room 104-A :On and/or before October 3, 2022 two orange portable power extension cords were used as a substitute for fixed wiring to charge electronic equipment. Employee(s) were exposed to the potential for electrical shock and/or fire hazard(s).
Recent events (2)
  • — P (S) $0
  • — Z (S) $0

1910.305 J01 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 16, 2022
Abate by
Feb 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(j)(1)(iv): Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lamp holders or other electrical parts:   Building 1 Room 206: On or before October 3, 2022, employees performed various repairing tasks within the room and asses the air conditioning systems that were stationed on the second floor adjacent office space(s). Employer did not ensure that the light fixture overhead was free from condensation discharge due to closest proximity of the Heating Ventilation and Air Conditioning system. Employees were exposed to electrical shock and/or fire hazards.
Recent events (2)
  • — P (S) $0
  • — Z (S) $0

1910.22 A01

Other-than-serious 1 instance 7 exposed
Issued
Nov 16, 2022
Abate by
Nov 29, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition.  Building 1,Room 206: On or before October 3, 2022, Employees in this building utilized this room in order to store office and decorative items used for various purposes. Employer did not ensure that the space was cleaned and free from any obstruction for employee entrance. Employees were exposed to slip/trip and fall hazards.
Recent events (1)
  • — Z (O) $0

View Patten Reserve Center's full OSHA safety record →