SAIPAN, MP —
OSHA Inspection: TRIPLE J SAIPAN, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of TRIPLE J SAIPAN, INC. in SURFRIDER HOTEL BEACH ROAD, SAIPAN, MP 96950 (NAICS 721110). OSHA activity number 346295967.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TRIPLE J SAIPAN, INC.
- Site address
- SURFRIDER HOTEL BEACH ROAD
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- PMB 103 P.O. BOX 1000 SAIPAN MP, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 15
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.147 A03 I
- Issued
- Nov 30, 2022
- Abate by
- Dec 19, 2022
- Penalty
- Initial $5,283 · Current $2,642 Reduced
General-duty citation text
29 CFR 1910.147(a)(3)(i): The employer did not utilize procedures for affixing appropriate lockout devices or tagout devices to energy isolating devices, and to otherwise disable machines or equipment to prevent unexpected energization, start up or release of stored energy in order to prevent injury to employees. Outside of the Hotel: Employees performed routine maintenance on multiple air conditioning units without utilizing appropriate lockout devices. Employees were exposed to electrical, caught-in, and rotating part hazards.
Recent events (3)
- — F (O) $2641.5
- — C (S) $5283
- — Z (S) $5283
1910.303 B02
- Issued
- Nov 30, 2022
- Abate by
- Dec 12, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a. Maintenance office: The Project Architect's computer, phone, internet, and other electronics were plugged into two series connected "daisy chained" relocatable power taps. Employees were exposed to fire and electrical hazards. b. Maintenance office: The Project Architect's computer, phone, internet, and other electronics were supplied power from a relocatable power tap that was screwed to the wall. Employees were exposed to fire and electrical hazards. c. Maintenance office: A Cannon C5235a Multi-Function printer was supplied power by an extension cord series connected "daisy chained" to a relocatable power tap. Employees were exposed to fire and electrical hazards.
Recent events (1)
- — Z (O) $0
1910.303 G01
- Issued
- Nov 30, 2022
- Abate by
- Dec 12, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Electrical Room: The main electrical panel for the Surfrider Hotel was blocked by various materials. Access was restricted in the event of an emergency.
Recent events (1)
- — Z (O) $0
1910.305 B01 II
- Issued
- Nov 30, 2022
- Abate by
- Dec 19, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Outside of the south wing: A knockout was missing from the bottom right side of the electrical box providing power to the Gree Split Type Air Conditioner model GWC36LB-D3DNAG/O. Employees were exposed to electrical hazards.
Recent events (1)
- — Z (O) $0
1910.305 C04
- Issued
- Nov 30, 2022
- Abate by
- Dec 19, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface: a. Electrical Room: The light switch controlling power to the overhead lights had a missing faceplate. Employees were exposed to electrical hazards. b. IT Room: The light switch controlling power to the overhead lights had a missing faceplate. Employees were exposed to electrical hazards.
Recent events (1)
- — Z (O) $0
1910.1200 E01 I
- Issued
- Nov 30, 2022
- Abate by
- Dec 19, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1)(i): The employer did not compile a list of the hazardous chemicals known to be present using a product identifier that was referenced on the appropriate safety data sheet. Carpenter Shop: A list of all hazardous chemicals maintained within the carpenter shop was not developed. Employees were exposed to chemical hazards.
Recent events (1)
- — Z (O) $0
1910.1200 G08
- Issued
- Nov 30, 2022
- Abate by
- Dec 19, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical Carpenter Shop: The safety data sheets for Boysen Clear Gloss Lacquer, Ace Rust Stop, Varathane Wood Stain and various other chemicals in the Carpenter shop were not maintained. Employees were exposed to chemical hazards.
Recent events (1)
- — Z (O) $0
More inspections at Triple J Saipan, INC.